Technical Manual Switch Actuators AMI/AMS
 
The available settings for a load monitoring are shown at the following chart: 
ETS‐text 
Factor for load monitoring 
x100mA 
Hysteresis % 
Behavior at 
exceeding/deviating 
Behavior at not 
exceeding/deviating 
Send exceeding/deviating 
cyclical 
Table 33: Monitoring exceedance/deviation of load 
 
The reference value for the observation is set by the parameter "Factor for load monitoring". The 
adjusted value is multiplied with 100mA, so the value can be adjusted in the range of 0,1A to 20A 
with 100mA steps. The hysteresis, which is indicated in % of the reference value, can avoid a too fast 
switching. At the monitoring exceedance of load, the hysteresis is subtracted from reference value. 
At the monitoring lower deviation of load, the hysteresis is added to the reference value. But the 
switch‐on value is always the same as the reference value only the switch‐off value is calculate by the 
upper way: 
So, for a hysteresis of 10% and a reference value of 1A, the following switching points will result: 
At the exceedance of load, a value is sent at exceedance of 1A, which only is reset when the value 
deviates above 0,9A. 
At the deviation of load, a value is sent at deviating 1A, which only is reset when the value exceeds 
above 1,1A. 
The sending conditions of the according communication object can also be adjusted. The telegram 
can send as well on‐telegrams as off‐telegram for the different cases. Additional the object can sent 
no telegram. Also, a cyclic sending can be activated. 
 
The following chart shows the relevant communication objects: 
Number 
Name 
12 
Exceedance of load 
13 
Lower deviation of load 
Table 34: Communication objects load deviation/exceedance 
 
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
41
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Dynamic range 
[default value] 
1‐200 
[1] 
10‐100 
[10] 
 Send no telegram 
 Send On‐telegram 
 Send Off‐telegram 
 Send no telegram 
 Send On‐telegram 
 Send Off‐telegram 
 not active 
 15min 
 30min 
 60min 
 90min 
 120min 
Length
Usage
1 Bit 
reports an exceedance of load 
1 Bit 
reports an deviation of load 
 
comment 
adjusts the reference value for the 
monitoring of load 
Adjustment of the hysteresis for 
avoiding to fast switching 
Adjustment of the behavior, when the 
measured value is out of the adjusted 
range 
Adjustment of the behavior, when the 
measured value is in the adjusted range 
Activation and adjustment of the time 
step for a cyclic sending 