Technical Manual Switch Actuators AMI/AMS
4 Reference ETS‐Parameter
4.1 General Settings
The following parameter exists only once and affects to all channels:
Figure 5: General settings
The parameter startup timeout adjusts the time between an upload and the functional start of the
device. The used hardware reacts only after expiration of the adjusted time. All input commands
before the startup timeout expire. Furthermore an "Operating" telegram and a telegram for the
group state can be activated. The "Operating" telegram sends cyclic whether the actuator answers at
the bus or not, so the debugging of greater objects become much easier. The group state sends the
state of all channels as 4 Byte telegram, which can be used for visualizations.
The following chart shows the dynamic range of this parameter:
ETS‐text
Startup timeout
Cyclic send of "Operating"‐
Telegram
Send group state
Total current
Table 7: General settings
The following chart shows the relevant communication objects:
Number
Name
Operating
Group state
Table 8: Communication objects general functions
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
13
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Dynamic range
[default value]
1‐60s
[1s]
no send, 10min, 30min, 1h,
3h, 6h, 12h, 24h
not active, on request, on
changes, on changes and cyclic
5min/ 19min/ 30min/ 1h/ 2h/
4h
active
not active
Length
Usage
1 Bit
sends cyclic, if the actuator is at the bus
4 Byte
sends the state of all channels
comment
Time between an upload and the
functional start of the device
activates the cyclic sending of the
"Operating" telegram if the
actuator answers at the bus
sends the states of all channels as
4 Byte telegram
activates the total current
measurement, have a look at
chapter 4.6.2 total current