Manual Control And Cyclic Send Of The Current State - MDT AMI series Technical Manual

Switch actuators with current measurement
Table of Contents

Advertisement

Technical Manual Switch Actuators AMI/AMS
 
4.3.5 Manual control and cyclic send of the current state
 
The following illustration shows the available settings for the manual control and the cyclic sending: 
Figure 11: Manual control and cyclic send 
 
The following chart shows the dynamic range for this parameter: 
ETS‐text 
Manual control 
Send cyclic the current state 
value 
Table 16: Manual control and cyclic send 
The manual control can be activated or deactivated permanent for each channel, by the settings 
"active" or "not active". Additional the manual control can be blocked or enabled via the central 
object "manual control". There is only one central object for every channel. This object blocks the 
manual control, by a logical "1", at every channel with the setting "activate via object". 
The setting "Send cyclic the current state value" activates the cyclic send of the state of the channel 
via its status object. 
 
The following chart shows the relevant communication objects: 
Number 
Name 
State 
 
Manual control 
Table 17: Communication objects manual control and cyclic send 
 
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
19
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Dynamic range 
[default value] 
active 
not active 
activate via object 
(Value 1 = not active) 
no send cyclic 
5min 
10min 
20min 
30min 
1h 
2h 
4h 
Length
Usage
1 Bit 
Status object for the corresponding channel 
1 Bit 
blocks the manual control in the channels with 
activated function 
 
 
 
comment 
activates or deactivates the 
manual control, also 
switchable via the central 
object „manual control" 
activates the cyclic send of the 
current value 
If activated, the current state 
will be send cyclic at the 
adjusted time steps via the 
object Channel X: state 

Advertisement

Table of Contents
loading