Technical Manual Switch Actuators AMI/AMS
The chart shows all possible settings for staircase outputs:
ETS‐text
Mode
Time for staircase [s]
Prewarning
Warning time [s]
Prewarning time [s]
Manual switching off
Extend staircase time
Central function
Behavior when locked
Behavior when unlocked
Behavior at bus power down
Behavior at bus power up
Table 24: Parameter staircase
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
31
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Dynamic range
[default value]
normally opened
normally closed
0...65535 sec
[120 sec]
not active
active
0...65535 sec
[120 sec]
0...65535 sec
[120 sec]
not active
active
not active
active
not active
active
Off
On
no change
Off
On
no change
Off
On
no change
Off
On
no change
comment
Operation mode of the channel
Duration of the switching process
Activates the prewarning function
Duration of the warning;
Only available when warning is activated
Adjustment, how long the light shall be
switched on after the warning;
Whole duration of the warning process is
the sum of the 3 times: Staircase time,
warning and prewarning
Only available when warning is activated
Activation of the manual turn off of the
staircase
Activation of the extension of the
staircase
Activates the central function for this
channel
Action for activating the blocking process
Action for deactivating the blocking
process
Action for a bus power breakdown
Action for a bus power return