4.4.4 Scene function
 
When functions of different groups (e.g. light, heating and shutter) shall be changed simultaneously 
with only one keystroke, it is practical to use the scene function. By calling a scene, you can switch 
the lights to a specific value, drive the shutter to an absolute position, switch the heating to the day 
mode and switch the power supply of the sockets on. The telegrams of these functions can have as 
well different formats as different values with different meaning (e.g. "0" for switch the lights off and 
open the shutters). If there were no scene function, you would have to send a single telegram for 
every actuator to get the same function. 
The scene function of the switch actuator enables you to connect the channels of the switch actuator 
to a scene control. For that, you have to assign the value to the appropriated space (scene A..H). It is 
possible to program up to 8 scenes per switching output. When you activate the scene function at 
the switching output, a new sub menu for the scenes appears at the left drop down menu. There are 
settings to activate single scenes, set values and scene numbers and switch the memory function 
on/off at this sub menu. 
Scenes are activated by receiving their scene numbers at the communication object for the scenes. If 
the memory function of the scenes is activated, the current value of the channel will be saved at the 
called scene number. 
The communication objects of the scenes have always the length of 1 byte. 
 
The following illustration shows the setting options at the ETS‐Software for activating the scene 
function: 
Figure 16: Scene function 
 
The following chart shows the relevant communication object: 
Number 
Name 
Scene 
Table 21: Communication object scene 
 
For calling a certain scene, you have to send the value for the scene to the communication object. 
The value of the scene number is always one number less than the adjusted scene number. For 
calling scene 1, you have to send a "0". So the scene numbers have the numbers from 1 to 64, but 
the values for the scenes only from 0 to 63. 
If you want to call scenes by a binary input or another KNX device, you have to set the same number 
at the calling device as at the receiving device. The calling device, e.g. a binary input, sends 
automatically the right value for calling the scene. 
 
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
25
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de