MDT AMI series Technical Manual page 17

Switch actuators with current measurement
Table of Contents

Advertisement

Technical Manual Switch Actuators AMI/AMS
 
The blocking function gets active, when the corresponding communication object becomes a logical 
"1". By sending a logical "0", the blocking function can be deactivated again. 
The parameter "Behavior when locked" defines an action for the output at activating the blocking 
process. There are the setting on, off and no change available. The same settings are also available 
for the "Behavior when unlocked". This action is called when the blocking function is deactivated 
again. 
 
The following chart shows the corresponding communication object: 
Number 
Name 
Block 
Table 14: Communication object blocking function 
The following diagram describes the blocking process. For the "Behavior when locked", the action on 
was parameterized and for the "Behavior when unlocked" the action off was parameterized: 
 
The KNX telegram shows which values are send to the blocking object. By sending a logical "1", the 
blocking function is activated and the channel is switched on. The blocking function is deactivated 
again by sending a logical "0". So the channel is switched off. 
 
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
17
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Length
Usage
1 Bit 