3.3 Communication Objects current measurement
 
The following communication objects are available for the current measurement and counting of the 
operating hours: 
Nr. 
Function 
Response operating 
hours 
Time to the next service 
Reset operating hours 
Reset service 
10  
Service required 
11 
Current value 
12 
Exceedance of load 
13 
Lower deviation of load 
14 
Fault current 
14 
Load faulty 
14 
Fault current/Load faulty  reports a fault current and a fault of 
15 
Reset power meter 
16 
Active energy 
+18 
next channel 
75/147  Total active energy 
76/148  Value of total current 
77/149  Exceedance of total 
current 
Table 5: Communication objects current measurement 
 
The sizes as well as the type of the shown objects depends to the adjusted parameterization, have a 
look at the relevant explanations at section 4. 
There are objects for the current measurement of the single channels as well as for the total current 
measurement of the actuator. It can be adjusted whether a channel shall be included to the total 
current measurement or not. 
 
 
 
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
11
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Usage 
reports counted operating hours 
reports time to the next service 
resets counter for the operating hours  DPT 1.001 
resets the counter for the service time  DPT 1.001 
reports required maintenance 
reports the actual current 
consumption of the channel 
reports an exceeded load 
reports an underranged load 
reports a fault current 
reports a fault of the load 
the load 
resets the calculated energy of the 
channel 
sends the calculated energy of the 
channel 
sends the sum of the calculated 
energy 
reports the total current of all 
activated channels 
reports an exceeded load of all 
activated channels 
 
Data type 
 
Out, Read 
DPT 7.007 
DPT 7.007 
Out, Read 
In, Write 
In, Write 
DPT 1.001 
Out, Read 
DPT 7.012/ 
Out, Read 
DPT 9.021/ 
DPT 14.019/ 
DPT 9.024 
DPT 1.001 
Out, Read 
DPT 1.001 
Out, Read 
DPT 1.001 
Out, Read 
DPT 1.001 
Out, Read 
Out, Read 
DPT 1.001 
In, Write 
DPT 1.001 
Out, Read 
DPT 13.010/ 
DPT 13.013 
Out, Read 
DPT 13.010/ 
DPT 13.013 
DPT 9.021/ 
Out, Read 
DPT 14.019/ 
DPT 9.024 
Out, Read 
DPT 1.001 