Technical Manual Switch Actuators AMI/AMS
4.6.2 Power meter function
The power meter function can be activated for each channel and can be parameterized further
afterwards:
Figure 27: Power meter function
The following chart shows the available settings for this parameter:
ETS‐text
Object selection for power
meter
Sending object value
Figure 28: Settings power meter function
The power meter counts the active energy of the channel according to the adjusted voltage and the
measured current. The intern count is continuous but the output rises only up every 10Wh.
Via the object "Reset power meter", the power meter can be set to zero again.
So the power meter function offers an effective method for observing the power consumption of
devices at determined cycles (day, week, month). An additional visualization of the power
consumption can help saving energy and switch devices on demand.
The following chart shows the relevant communication objects:
Number
Name
15
Reset power meter
16
Active energy
Table 28: Communication object meter
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
37
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Dynamic range
[default value]
Value in Wh (DPT 13.010)
Value in kwh (DPT 13.013)
only request
send cyclic 10min/ 30min/
1h/ 3h/ 6h/ 12h/ 24h
Length
Usage
1 Bit
resets the power meter to zero again
4 Byte
sends the measured energy
comment
Selection of the sending object for the
power meter
defines the sending condition for the
calculated power