P0003 Parameter access level
0
Customized Parameter List; see P0013
1
Standard: Access to most commonly used
parameters (factory setting)
2
Extended: Extended access, e.g., to VSD
I/O functions
3
Expert:
For experienced users only
4
Service:
For authorized service personnel only
(password protected)
P0010 Start quick commissioning
0
Ready for operation
1
Quick commissioning
30 Factory setting
Note
Always reset P0010 to "0" before operating the motor.
If, after commissioning, P3900 = 1 is set, this is done
automatically.
P0100 Operation for Europe/North America
0
Power in kW; f default 50 Hz
1
Power in hp; f default 60 Hz
2
Power in PS; f default 60 Hz
Note
Use the DIP switch for settings 0 & 1 to allow for a
permanent setting.
P0304 Rated motor voltage
10 V – 2000 V
Rated motor voltage (V) from rating plate
P0305 Rated motor current
0 – 2 x VSD rated current (A)
Rated motor current (A) from rating plate
P0307 Rated motor power
0 kW – 2000 kW
Rated motor power (kW) of rating plate.
If P0100 = 1, the values are output in hp
P0310 Rated motor frequency
12 Hz – 650 Hz
Rated motor frequency (Hz) from rating plate
P0311 Rated motor speed
0 – 40.000 U/min
Rated motor speed (U/min) from rating plate
Siemens Building Technologies
HVAC Products
Quick commissioning flow chart
1
)
)
1
)
1
)
1
)
1
)
1
Motor-specific parameters – see drawing of motor rating plate below.
2
)
Indicates parameters incorporating detailed lists of possible settings for use in special site applications.
Refer to the engineering manual and operating instructions.
SED2 variable speed drives
Commissioning
P0700 Selection of command source
(on / off / reverse)
0
Factory setting
1
Basic operator panel
2
Terminal / digital inputs
P1000 Selection of frequency setpoint
0
No frequency setpoint
BOP frequency control ↑↓
1
2
Analog setpoint
P1080 Min. motor frequency
Sets the minimum motor frequency (0 – 650 Hz) at
which the motor runs irrespective of the frequency
setpoint. The value set here applies to both directions
of rotation.
P1082 Max. motor frequency
Sets the maximum motor frequency (0 – 150Hz) at
which the motor runs irrespective of the frequency
setpoint. The value set here applies to both directions
of rotation.
P1120 Ramp-up time
0 s – 650 s
Time taken for the motor to accelerate from standstill
to maximum motor frequency.
P1121 Ramp-down time
0 s – 650 s
Time taken for the motor to decelarate from maximum
motor frequency to standstill.
P3900 End quick commissioning
0
No quick commissioning (factory setting)
1
End quick commissioning with motor calculation
and resetting all other parameters to the factory
setting (recommended)
2
End quick commissioning with motor calculation
and I/O reset (recommended)
3
End quick commissioning with motor calculation
but without I/O reset
)
2
)
2
47/126