Setting 99 (BICO) is intended for experienced users only.
For more detailed information, refer to the SED2 engineering manual.
Factory settings:
P0707 to P0708
Analog inputs 1 and 2 can be reconfigured with parameters P0707 and P0708 as
digital inputs if required.
The following limit values apply to analog inputs configured as digital inputs:
1.6 VDC = Off.
4.0 VDC = On.
Factory setting: 0
DIN7
Connection of the two analog inputs for use as additional digital inputs DIN7 and DIN8.
P0725
Operating mode for the digital inputs NPN or PNP
This parameter determines whether the digital inputs DIN1 to 6 are to be enabled by
"logic 0" or "logic 1".
Possible settings:
0
NPN mode
Þ
1
PNP mode
Þ
r0722
Check of the digital and analog inputs
This parameter can be used to check the functions of the digital and analog inputs. You
can check the presence of a signal at the channel.
When an active signal is present, the associated segment of the display lights up. The
allocation of each of the inputs to a specific segment is illustrated below.
SED2 variable speed drives
Programming
P0701
1
ON / OFF1.
P0702
12
Reverse (change dir. of rotation).
P0703
9
Error acknowledgement.
Fixed setpoint (binary coded).
P0704
15
Fixed setpoint (binary coded).
P0705
15
P0706
3
OFF2 – coast to standstill.
1
2
3
DIN8
4
active low.
active high (factory setting).
DIN6 DIN5
DIN2 DIN1
AIN2 AIN1
DIN4 DIN3
1
2