Parameterizing the PID
controller
Siemens Building Technologies
HVAC Products
Set the scaling of the actual value for analog input 2
(see section 6.3.2 Analog inputs).
Set to 755[1] (defines AIN2as actual value).
Define the reaction of the PID controller to the actual values (0=heating,
1=cooling).
Enable the PID controller (0=disable, 1=enable).
Check for setpoint (scaled PID setpoint in %).
Note: VSD must be set to automatic control.
DIN1 must be set to ON.
Check for actual value (scaled PID actual value in %).
Set and optimize P2280 PID proportional gain and P2285 PID integration time.
Changeover to automatic control .
6.4.2

Belt failure detection without sensor (P2181)

SED2
This function allows for monitoring power transmission components such as drive belts.
The function can also detect motor overload, e.g. in the case of jam.
The actual frequency / torque curve is compared to a preprogrammed tolerance band
(see P2182 to P2190) as part of this function. If the actual curve is outside the
tolerance band, a warning or error message is generated.
SED2 variable speed drives
Programming
P0757[1] to P0760[1]
P2264
P2271
P2200
r2262
r2272
Motor
Fan
5192Z22en
65/126
CM1U5192en
01.2002