Controls, Settings, And Functions - Daikin RDT-135c Installation And Maintenance Manual

Roofpak series singlezone roof mounted heating and cooling units
Table of Contents

Advertisement

Introduction: Controls, Settings, and Functions

Controls, Settings, and Functions

Table 3 below lists all of the unit control devices. Included in
the table are the device symbol, a description of the device, its
function, and any reset information, its location, any device
Table 3: Controls, settings, and functions
Symbol
Description
CS1 & 2 Switch (toggle),
Shuts off compressor control
refrigerant circuit
circuits manually
DAT
Discharge air
Senses discharge air
temperature
temperature
sensor
DHL
Duct high limit
Prevents excessive VAV duct
switch
pressures; shuts off fan
EFT
Entering fan air
Senses entering fan air
temperature
temperature
sensor
FP1, 2 Evaporator frost
Senses low refrigerant
protection
temperature
FS1
Freezestat
Shuts off fans, opens heating
valve, and closes outdoor
damper if low air temperature
at coil is detected
HP1, 2,
High pressure
Stops compressor when
3 & 4
control
refrigerant discharge pressure
is too high
LP1, 2 Low pressure
Stops compressor when
control
suction pressure is too low
(used for pumpdown)
MCB
Main control board Processes input information
MP1–6 Compressor
Senses motor winding
motor protector
temperature, shuts off
compressor on high
temperature.
Notes:
1.Unit size 018C compressors
include internal motor
protector.
2.Unit sizes 020C–036C,
circuit #1 compressors include
internal motor protector (refer
to unit wiring diagram).
OAE
Enthalpy control
Returns outside air dampers to
(electro-
minimum position when
mechanical)
enthalpy is too high
Enthalpy control
Returns outside air dampers to
(electronic)
minimum position when
outside air enthalpy is higher
than return air empalthy
(use RAE)
OAT
Outside air
Senses outside air
temperature
temperature
sensor
PC5
Dirty filter switch
Senses filter pressure drop
PC6
Dirty filter switch
Senses filter pressure drop
18
Function
Reset
N/A
N/A
Discharge air
Auto
N/A
Inlet of supply
N/A
Return bends
Auto
Manual
(relay
latched)
Auto
N/A
Auto at
3400
ohms
Auto
Auto
N/A
Auto
Auto
setting, any setting ranges, differentials, and the device part
number.
Location
Setting
Main control
N/A
panel
N/A
section
Main control
3.5" w.c
panel
(871.8 Pa)
N/A
fan
Opens at 30°F
of
Closes at 45°F
evaporative
coil
Heating
38°F (3°C)
section
or as required
Compressor
See page 117.
Compressor
See page 117.
Main control
N/A
box
Compressor
9 K–18 K ohms
junction box
Economizer
"B" or as required
section
Economizer
Fully CW past "D"
section
(when used
with RAE)
N/A
First filter
As required
section
Final filter
As required
section
Range
Differential
N/A
N/A
N/A
0.05–5.0" w.c.
.05" w.c.
(12.5–1245.4 Pa)
(12.5 Pa), fixed
N/A
N/A
N/A
35°F–45°F
12°F (7°C),
(2°C–7°C)
fixed
N/A
100 psi
(689 kPa)
N/A
25 psi
(172 kPa)
N/A
N/A
700 ohms cold
N/A
A–D
Temperature:
3.5°F (2°C)
Humidity:
5% fixed
A–D
N/A
N/A
.05-5" w.c.
.05" w.c.
(12.5–1245.4 Pa)
(12.5 Pa)
.05-5" w.c.
.05" w.c.
(12.5–1245.4 Pa)
(12.5 Pa)
Part no.
01355000
060004705
065493801
060004705
072501901
065830001
047356120
047356111
060006101
044691509
030706702
049262201
060004705
065493801
065493801
IM 738-2