Mechanical Installation: RPS Factory Split at Fan
RPS Factory Split at Fan
Field reassembly of an RPS/RDT unit that has shipped split at
the fan takes place in three phases: (1) setting the sections
(2) mechanically recoupling the cabinet, and (3) reconnecting
power and control wiring.
(
Phase I. Set sections
Figure 38
Remove top cap and save for Step 3.
1
Figure 38. Set sections
Remove top cap and
save for reassembly.
Fan end of unit
30
)
Remove plywood and retaining
angles from unit and discard.
Discharge end of unit
Remove screws on fan panel,
leaving retainer clips in place.
Save screws for reassembly.
Remove screws on fan panel, leaving retainer clips in place
2
to secure bulkhead. Save screws for Phase II, Step5.
3
Remove plywood and retaining angles from unit and
discard.
4
Carefully lower both sections of unit (fan end and
discharge end) into place, making sure the roof curb
engages the recesses in the unit base.
IM 738-2