Daikin RDT-135c Installation And Maintenance Manual page 29

Roofpak series singlezone roof mounted heating and cooling units
Table of Contents

Advertisement

Lifting Points
To determine the required lifting cable lengths and whether
four-or six-point lifting is required, use Tables 8 and 9 and
Figures 33 and 34.
Referring to Figure 33 and Figure 34, note that dimension A is
the distance between the outer lifting points. The four outer
rigging cables must be equal to or longer than dimension A.
Dimension B shows the minimum distance between the outer
and the inner lifting points for six-point lifting. Use this to
roughly determine the required length of the middle cables for
six-point lifting. Determine dimension A by subtracting
dimensions X and Y from dimension Z (e.g., A = Z – X – Y).
Table 8: X dimension (Figure 33 and Figure 34)
Outdoor/return air section
100 O.A.
Plenum
0–30% O.A.
0–100% economizer
0–100% economizer with 15" return fan
0–100% economizer with 30" return fan
0–100% economizer with 40" return fan
0–100% economizer with return fan
Table 9: Y dimension (Figure 33 and Figure 34)
RPS unit size
015C–030C
036C & 040C
045C–090C
105C
115C–135C
IM 738-2
015C–030C
in
mm
0
0
40
1016
40
1016
40
1016
62
1575
52
1321
Dimension Y
49.5" (1257 mm)
38.2" (970 mm)
39.5" (1003 mm)
30.5" (775 mm)
39.5'" (1003 mm)
Mechanical Installation: Rigging and Handling
Where:
Z = Total unit length in inches
(refer to certified drawings for this dimension).
X = Outdoor/return air section length (refer to Table 8for this
dimension).
Y = Refer to Table 9 for this dimension (see Figure 33 and
Figure 34).If A ≤ 288" (7315 mm), 4-point lifting is sufficient.
If A > 288" (7315 mm), 6-point lifting is required.
036C–040C
045C–075C
in
mm
in
0
0
0
52
1321
48
52
1321
48
52
1321
72
52
1321
80
2032
72
Figure 33. Unit type RPS/RDT lifting points
080C–135C
mm
in
mm
0
0
0
1259
72
1829
1259
72
1829
1829
96
2438
1829
96
2438
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents