Table 15: Approximate 407C refrigerant charge per circuit, 015C to 040C
lbs per circuit (less DX coil)
Unit size
Circuit 1
015C to 018C
10
020C
10
025C
21
030C
21
036C
29
040C
30
* Condenser pumpdown capacity is the total charge for both circuits and is based on volume between condenser
entrance and liquid line solenoid at 90°F, 90% full
Table 16: Approximate R407C refrigerant charge per circuit, 045C to 135C
Unit size
Circuit #1
045C
31
050C
31
060C
32
070C
36
075C
36
080C
37
090C
42
105C
46
115C
54
125C
—
135C
—
* DX coil configuration (S = Standard, L = Large) is identified by the 8th digit of the RPS/RDT or RFS model number, found on the unit nameplate. For example,
DX = L for unit model number RFSO6OCLY.
* Condenser pumpdown capacity is the total charge for both circuits and is based on volume between condenser entrance and liquid line solenoid at 90º F,
90% full.
Table 17: Weight of refrigerant in copper lines (pounds per 100 feet of Type L tubing)
Vol. per 100 ft.
O.D. line size
in cubic feet
3/8"
0.054
1/2"
0.100
5/8"
0.162
7/8"
0.336
1 1/8"
0.573
1 3/8"
0.872
1 5/8"
1.237
2 1/8"
2.147
2 5/8"
3.312
3 1/8"
4.728
3 5/8"
6.398
4 1/8"
8.313
IM 738-2
Base charge
Evaporator coil
(lbs/CKT/coil row)
Circuit 2
16
16
20
19
29
29
Base charge
lbs per circuit (less DX coil)
RPS
Circuit #2
Circuit #1
30
31
30
32
31
32
36
37
36
37
37
34
43
41
42
41
55
55
55
—
55
—
Liquid @100°F
R22
R407
3.84
3.64
7.12
6.74
11.53
10.92
23.92
22.65
40.80
38.62
62.09
58.77
88.07
83.37
152.87
144.71
235.81
223.23
336.63
318.67
455.54
431.23
591.89
560.30
Mechanical Installation: RFS/RCS Permanent Split Systems