Electrical Installation: Field Power Wiring
In compliance with the National Electrical Code, an
electrically isolated 115V circuit is provided in the unit to
supply the factory mounted service receptacle outlet and
optional unit lights. This circuit is powered by a field
connected 15A, 115V power supply. Leads are brought into the
RFS and RPS units through a 7/8" knockout in the bottom of
the main control panel, near the power wire entry point.
Figure 66. RCS 015C–030C power wiring connections
Conduit and hub
(shipped with
RCS unit)
Power block PB4
or disconnect
switch DS4
7/8" knockout for
wire entry (field to cut
larger holes as required
for power wire)
Figure 67. RCS 036C and 135C power wiring connections
(number of condenser fans varies per unit size)
Conduit and hub
(shipped with
RCS unit)
Power block PB4
or disconnect
switch DS4
7/8" knockout for
wire entry (field to cut
larger holes as required
for power wire)
54
7/8" knockout for
TB8 wire entry
Terminal block TB8
for 115V service
receptical circuit
7/8" knockout for
TB8 wire entry
Terminal block TB8
for 115V service
receptical circuit
Table 21: Multiple point power connection options
Number of
Disconnect
electrical
designation
circuits
2
DS2
DS1
2
DS3
DS1
3
DS3
DS2
DS1
Table 22: Recommended 3-phase power wiring to ensure
disconnects and power blocks mate with power wiring
Insulation
Wire
Qty./
rating
gauge
pole
(°C)
10
1
75
8
1
75
6
1
75
4
1
75
3
1
75
2
1
75
1
1
75
1/0
1
75
2/0
1
75
3/0
1
75
4/0
1
75
250
1
75
300
1
75
350
1
75
400
1
75
500
1
75
3/0
2
75
4/0
2
75
250
2
75
300
2
75
350
2
75
400
2
75
500
2
75
250
3
75
300
3
75
350
3
75
Notes:
1. All wire sizes assume separate conduit for each set of parallel conductors.
2. All wire sizes based on NEC Table 310-16 for 75°C THW wire (copper).
Canadian electrical code wire ampacities may vary.
3. All wire sizes assume no voltage drop for short power leads.
Location
Load
(see Figure 12
on page 10)
Supply and return fan
Main control panel
motors plus controls
Balance of unit
Main control panel
Electric heat
Electric heat
control panel
Balance of unit
Main control panel
Electric heat
Electric heat
control panel
Supply and return fan
Main control panel
motors plus controls
Balance of unit
Main control panel
For MCA
No. of
Conduit
conduits
(trade size, in.)
1
1/2
1
3/4
1
1
1
1 1/4
1
1 1/4
1
1 1/4
1
1 1/4
1
1 1/2
1
2
1
2
1
2
1
2 1/2
1
2 1/2
1
3
1
3
1
3
2
2
2
2
2
2 1/2
2
2 1/2
2
3
2
3
2
3
3
2 1/2
3
2 1/2
3
3
up to
(amps)
35
50
65
85
100
115
130
150
175
200
230
255
285
310
335
380
400
460
510
570
620
670
760
765
855
930