AKD PROFINET | 3 Installation and Setup

3.4.1 Dependency Service Channel (WorkBench) and PROFINET

WorkBench and PROFINET use the same IP communication channel to communicate with
the drive so changing the IP address has implications for both interfaces.
There are several options for assigning the IP address for WorkBench and PROFINET as
described in the AKD User Guide:
DHCP, AutoIP
l
Static IP addressing
l
o
o
PROFINET Devices (only): DCP
l
Once you have changed the IP address via DCP (e.g. through the steps above), the IP.* para-
meters stored in the drive are overwritten. Should you need to use DHCP or static IP address-
ing later, you must use WorkBench to set, the IP.MODE to something other than 1. See AKD
User Guide for details on the mode you would like to use.

3.4.2 Reset of IP Address Parameters

If the AKD can not be found in the network, as a last resort, reset all IP address parameters
to their default values.
This is done by setting the rotary switches to 0 and holding the B1 button longer than 5
seconds. After this, the current IP address setting will be lost and the IP address is restored
to default settings (after power cycle):
If rotary switches are zero, the DHCP and AutoIP is enabled.
If rotary switches are not zero, the static IP address is 192.168.0.xx (xx rotary switches) and
subnet mask 255.255.255.0.
14
Kollmorgen | kdn.kollmorgen.com | November 2018
Via rotary switches (Address area 192.168.0.xx)
Via ASCII commands IP.ADDRESS, IP.SUBNET. IP.GATEWAY