Vacon X5EIP01 Installation Manual page 9

Ethernet ip option board with 115 vac encoder interface, x series

Advertisement

10
vacon
Getting Started
To begin communicating with the drive over Modbus / TCP, the drive's IP address must be set (use parameters 922-
925). After setting the IP address, cycle power off and on for the new address to take effect.
For information on setting parameters, see the X5 User's Manual.
I/O Messaging
Input / Output (I/O) polling messages are for time-critical, control-oriented data. The messages are transferred
between the devices all the time and are used for continuous control of the frequency converter. They provide a
dedicated, special-purpose communication path between a producing application (master) and one or more
consuming applications (slaves). They are exchanged across single- or multi-cast connections and typically use
high-priority identifiers.
The polling message flow is shown in Figure 6.
Master
Figure 6: Polling Message Diagram
I/O messages 20, 21, 70, and 71 are standard Common Industrial Protocol (CIP) assemblies.
I/O messages 121, 122, 131, 132, 171, 172, 181, and 182 are vendor-specific messages that allow for customized
assemblies.
The values of the following parameters indicate which drive parameters are read or written to by the I/O assembly:
Parameter #
Parameter Name
880
FBus Read 1
881
FBus Read 2
882
FBus Read 3
883
FBus Read 4
884
FBus Read 5
890
FBus Write 1
891
FBus Write 2
892
FBus Write 3
893
FBus Write 4
894
FBus Write 5
Examples 1 and 2 on the following pages show how using the FBus Write 2 = Parameter 402 would allow the I/O
assembly to set the drive's acceleration rate.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board
Data (Output Assembly)
Data (Input Assembly)
Table 5: Parameter Assignments (Parameters 880-894)
Range
0-65535
0-65535
Default
103 (Output Voltage)
104 (Output Current)
105 (Drive Load)
107 (Drive Temp)
909 (DI Status)
103 (Output Voltage)
104 (Output Current)
105 (Drive Load)
107 (Drive Temp)
909 (DI Status)
Slave