Connecting The D9068; Input Point Connections; Figure 7: Molex Connector Descriptions - Bosch D9068 Operation And Installation Manual

Fire communicator
Table of Contents

Advertisement

.
The FACPs using open collector outputs must be compatibility listed. When
installing the D9068 more than 20 ft (6 m) from the FACP, configure the
inputs for supervised operation. The D9068 can be installed up to 500 ft
(152 m) from the FACP.
2.2

Connecting the D9068

2.2.1 Input Point Connections

Remove all power before making or breaking any connections to the D9068.
Failure to do so can cause personal injury and/or damage to the
equipment.
When making connections to the D9068, refer to Figure 7 through Figure 13 on this
page through page 16.

Figure 7: Molex Connector Descriptions

3
1
2
+ + - - A B
19
1 - Red (Power +)
2 - Black (Power -)
3 - TXIA
4 - RXIB
5 - White/Brown (Input Point 1)
6 - White/Red (Input Point 2)
7 - White/Orange (Input Point 3)
8 - White/Yellow (Input Point 4)
9 - White/Blue (Input Point 5)
10 - Black
11 - Red
* Connect the relay to an input on the FACP for trouble annunciation.
The contact position shows an off-normal condition. Under normal
operation, the trouble relay is energized. C and NO are connected.
Bosch Security Systems, Inc. | 3/13 | F01U071094-07
D9068 | Operation and Installation Guide | 2.0
5
7
6
8
4
1 2 3 4 5
17
18
11
9
12
10
10
KEYPAD
16
12 - Green
13 - Yellow
14 - Terminal not used
15 - Common trouble relay
16 - Keypad programmer
17 - Inputs (refer to Table 3 on page 8
for input specifications)
18 - Serial connection pins
19 - Power (refer to Table 2 on page 7
for specifications)
Installation
13
NC C NO
14
15
*
13