D9068 | Operation and Installation Guide | 4.0 System Operation
Manual Test
Initiate a Manual Communications Test
from the D7033/FMR-DACT-KEYPAD. Refer to
Section 5.5.4
3- TEST
on page 50. When a Manual Test
is initiated, you are prompted to select
a telephone line (Line 1 or Line 2).
After you select a telephone line, a
Manual Test Report is sent to the
receiver using the specified telephone
line.
When the Manual Test Report is
successfully added to the report queue,
the message COMMUNICATOR INITIALIZING...
appears on the keypad. This message
remains until the D9068 tries to
transmit the report.
While the Manual Test Report is sent,
the keypad display updates to show which
telephone line is in use and which
transmission attempt is occurring. The
message COMMUNICATOR LINE 1, TRY 1
indicates Phone Line 1 for transmission
attempt 1.
After the report transmits successfully,
the keypad display updates to show
COMMUNICATOR PASSED. After this message
appears for 2 sec, the keypad emits a
brief tone and the rotating Test Menu
returns to the keypad LCD.
Unless it sends the report successfully,
the D9068 tries to send a Manual Test
Report twice. This can take up to 3 min.
The report priorities are reevaluated on
each phone call attempt. If a higher
priority event occurs while attempting a
Manual Test, the higher priority event
is sent on the following telephone call.
Refer to Appendix A:
Troubleshooting on page 51 for
information about error
messages or messages indicating
abnormal operating conditions.
24
Bosch Security Systems, Inc. | 3/13 | F01U071094-07