Figure 10: Dry Contact Input Point Wiring (Supervised); Figure 11: Dry Contact Input Point Wiring (Non-Supervised) - Bosch D9068 Operation And Installation Manual

Fire communicator
Table of Contents

Advertisement

.

Figure 10: Dry Contact Input Point Wiring (Supervised)

1 - D9068
2 - Power + (red)
3 - Power – (black)
4 - Point 1 (white and brown)

Figure 11: Dry Contact Input Point Wiring (Non-supervised)

1 - D9068
2 - Power + (red)
3 - Power – (black)
4 - Point 1 (white and brown)
For UL installations, non-supervised operation requires installation
within 20 ft (6 m) inside the conduit.
Bosch Security Systems, Inc. | 3/13 | F01U071094-07
D9068 | Operation and Installation Guide | 2.0
+
-
+
2
8
Power (+)
NO
Dry
Contact
C
Relay
NC
7
Panel Ground
Earth Ground
+
+
2
7
Power (+)
NO
Dry
Contact
C
Relay
NC
Panel Ground
Earth Ground
1
KEYPAD
-
1
2
3 4 5
A B
4
5
3
5- Keypad terminals
6 - Earth ground (green)
7 - EOL resistor: 2.21 k  , UL Listed,
Bosch (P/N: 25899)
8 - FACP
1
-
-
1
2
3 4 5
KEYPAD
A B
4
5
3
5- Keypad terminals
6 - Earth ground (green)
7 - FACP
Installation
NC C NO
6
NC C NO
6
15

Hide quick links: