D9068 | Operation and Installation Guide | Appendix F: D8024/D10024/D10024A Analog
FACP Operation
F.4.7 Reported Event to FACP Cause Mapping
Table 23 lists the events generated by a D8024 and D10024/D10024A Analog FACP and
the causes of the events.

Table 23: Analog Reports and Causes

Analog FACP
Event
Point Fire Alarm
Point
Supervisory
Alarm
Point Monitor
Alarm
Point Fire
Trouble
Point Fire Dirty
Report
Point Fire
Disable
System Test
System Test
Restore
Silence
Fire Drill
Open Reset
Low Battery
AC Fail
Auto Test
Off Normal at
Test
Phone 1 Trouble
Phone 1 Restore
Phone 2 Trouble
Phone 2 Restore
Manual Comm Test
Data Lost
EEPROM Failure
System Reboot
Reset
Trouble Input
Trouble Input
Restore
Equipment Fail
Equipment
Restore
72
Comments
Control panel
generated.
Control panel
generated.
Control panel
generated.
Control panel
generated.
Control panel
generated.
Control panel
generated.
Control panel
generated.
Control panel
generated.
Control panel
generated.
Control panel
generated.
Dialer generated.
Control panel
generated.
Control panel
generated.
Dialer generated.
Dialer generated.
Dialer generated.
Dialer generated.
Dialer generated.
Dialer generated.
Dialer generated.
Dialer generated.
Dialer generated.
Control panel
generated.
Control panel
generated.
Control panel
generated.
Bosch Security Systems, Inc. | 3/13 | F01U071094-07
Cause
There is a point zone alarm.
There is sprinkler supervisory input.
An alarm from the point is programmed as type =
monitor.
Any point trouble.
Any point is dirty.
Any point disabled.
The Walk Test or Output Test entered.
The Walk Test or Output Test exited.
Only Silence reported; resound not reported.
A fire drill initiated (local and remote).
The control panel reset.
A low battery is detected.
There is an AC Fail (after the control panel and
dialer time-outs).
An Auto Test is in progress.
Control panel trouble occurred when the Test
Report was sent.
There is trouble on Phone Line 1.
The line is restored.
There is trouble on Phone Line 2.
The line is restored.
The Communications Test is in progress.
There is a communication error.
There is an EEPROM failure.
All trouble and alarms are cleared. This message
is sent when the D9068 receives an all clear
message from the control panel after the control
panel resets.
Trouble.
Trouble is stored.
This message occurs for several trouble type
events. To identify the specific type of trouble
that the condition parameter uses, refer to Table
15
on page 59. Look for the Equipment Fail
(Restore) Reports. Not all events have an
equivalent Equipment Restore message.