Bosch D9068 Operation And Installation Manual page 39

Fire communicator
Table of Contents

Advertisement

.
1:
WAIT FOR DC
To access WAIT FOR DC, select
[0]: PROGRAM[2]: PROG TIMERS[1]: AC
FAIL DLY [1]: WAIT FOR DC.
Two input points must be programmed with
one set for AC Fail and the other for
Low Battery. When an AC Fail signal is
received on the AC Fail input, the D9068
waits for a low battery signal. The WAIT
FOR DC function causes the D9068 to wait
and then send the AC Fail and Low Batt
Reports simultaneously. The current
setting appears in parentheses on the
first line.
When a Low Battery input
followed by an AC Fail input
activates, the AC Fail Report
is sent immediately.
To set the D9068 to wait and send AC
Fail and Low Batt Reports
simultaneously:
1. Press [1] and then [# Command]. The
setting in parentheses reflects the
setting.
2. After programming this feature, press
[* Clear] to return to the Prog
Timers submenu.
2:
WAIT DLY TIME
To access WAIT DLY TIME, select
[0]: PROGRAM[2]: PROG TIMERS[1]: AC
FAIL DLY[2]: WAIT DLY TIME. This
option allows you to select the length
of time to wait after an AC Fail signal
is received before reporting the event
over the phone line.
When the AC Fail and Low
Battery events are present
together, the AC Fail event is
reported regardless of any wait
time.
Programming WAIT DLY TIME for
00 allows the D9068 to send an
AC Fail Report without delay.
To choose the length of time to wait
after receiving an AC Fail signal:
1. At the AC Fail Dly submenu, press [2]
to select 2: WAIT DLY TIME and then
press [# Command]. The window shows:
AC FAIL DLY (__)
(00-24 HRS): _____
2. The current setting appears in
parentheses on the first line. Enter
the time and then press [# Command].
Bosch Security Systems, Inc. | 3/13 | F01U071094-07
D9068 | Operation and Installation Guide | 5.0
3. After programming this feature, press
[* Clear] to return to the Prog
Timers submenu.
2: DISPLAY RATE
To access DISPLAY RATE, select
[0]: PROGRAM [2]: PROG TIMERS[2]:
DISPLAY RATE. This option allows you to
set the speed (in units of 0.25 sec) at
which the menu lines are updated on the
LCD.
To set the speed for updating the LCD
menu lines:
1.
At the Prog Timers submenu, press
[2] to select 2: DISPLAY RATE. The
window shows:
DSPLY RATE (__)
.25 X (1-16): _____
2. The current setting appears in
parentheses on the first line. Enter
the desired value and press
[# Command].
3. After programming this feature, press
[* Clear] to return to the Prog
Timers submenu.
5.4.3 PROG INPUTS
The PROG INPUTS option allows you to
program the five available inputs.
To program the programming inputs:
1. At the Prog Inputs submenu, enter the
point number you want to program and
press [# Command]. The window shows:
POINT NUMBER
(1-5): ___
When you enter the point number, the
display scrolls through the PROG
INPUT options:
PROG POINT (___)
1: CONFIGURE
2: SUPERVISED
2. Press the number key that corresponds
to your selection.
Press [Drill] to move to the next
point. For example, if you are
programming Point 2 and you press
[Drill], you go to the Point 3
setting.
Press [Disable] to return to the
previous point. For example, if you
are programming Point 2 and you press
[Disable], you go to the Point 1
setting.
Programming
39