Manual Test Report Failure; Reports In Queue; Error During Comm Test - Bosch D9068 Operation And Installation Manual

Fire communicator
Table of Contents

Advertisement

D9068 | Operation and Installation Guide | Appendix A: Troubleshooting
.
A.4

Manual Test Report Failure

If the D9068 fails to send the Manual
Test Report in two attempts, or the
[* Clear] key is pressed, the report
transmission is aborted. A COMM FAULT
message is not sent. The D7033/FMR-DACT-
KEYPAD emits a three-beep tone and the
message COMMUNICATOR FAILED appears.
After 2 sec the keypad display updates
to show CLEARING ALL REPORTS!! Any
report in the report queue, including
the Manual Test Report, is deleted. The
rotating Test Menu appears after 2 sec.
A.5

Reports in Queue

If any reports are in the queue, the
D7033/FMR-DACT-KEYPAD Keypad Programmer
shows the message REPORTS IN QUEUE
PLEASE WAIT. The D9068 waits for these
reports to be sent. If you press
[* Clear] on the keypad, the wait ends,
the keypad emits a three-beep tone, and
the keypad's LCD shows the message,
ERROR DURING COMM TEST. The rotating
Test Menu returns to the keypad's LCD
after showing the message for 2 sec.
When the report queue is empty, the
D9068 prompts you to select the
telephone line to be used (either Line 1
or Line 2). The D9068 can also prompt
you to alternate the telephone lines.
For details, refer to 1: TEST COMM in
Section 5.5.4 3- TEST on page 50.
When the third option (ALTERNATE) is
selected, the telephone line is switched
from the line used in the last Manual
Test Report to the other line. This
switch occurs whether you select the
line number or ALTERNATE. Pressing
[* Clear] instead of a selection key
switches between Line 1 and Line 2.
Sending an Auto Test does not affect the
telephone line sequence of the Manual
Test Report. When the line selection is
complete, the Manual Test Report is
added to the report queue.
If the report queue is full of reports
to send, a Data Lost Report is sent
unless one is already in the queue and
the Manual Test Report is not sent. The
Data Lost Report goes in the History Log
when it is added to the report queue.
A.6

Error During Comm Test

When a Manual Test is requested, the
D9068 verifies there is at least one
good telephone line. If not, the keypad
emits a three-beep tone and ERROR DURING
COMM TEST appears for 2 sec. The
rotating Test Menu returns to the keypad
LCD.