D9068 | Operation and Installation Guide | 5.0 Programming
1:
CONFIGURE
To access CONFIGURE, select
[0]: PROGRAM [3]: PROG INPUTS[1]:
CONFIGURE. This feature allows each
input to be set for one of seven
options:
Fire: When activated, the D9068 sends
a Fire Alarm Report. A restoral is
sent when the input is deactivated.
Water-flow: When activated, the D9068
sends a Water-flow Alarm Report. A
restoral is sent when the input is
deactivated.
Supervisory: When activated, the
D9068 sends a Supervisory Alarm
Report. A restoral is sent when the
input is deactivated.
Monitor: When activated, the D9068
sends a Monitor Report. A restoral is
sent when the input is deactivated.
System Fault: When activated, the
D9068 sends a Trouble Input Report.
If a point is configured for System
Fault, a window appears to determine
where the point faults. Refer to Step
2 in this procedure for setting and
input option. A restoral is sent when
the input is deactivated.
AC Failure: When activated, this
point shows AC FAILURE on the
keypads. To decrease the number of
reports sent to the central station
such as during a blackout, program
the D9068 with an AC Fail Delay
between 0 and 24 h.
You can also program the D9068 to
Wait for DC. When programmed to wait
for DC, the D9068 must detect an AC
failure on one input and a low
battery condition on a second input.
If there are an AC fail input and a
battery input, the D9068 monitors
both inputs. If an AC failure occurs
and the delay time is initialized,
the D9068 looks for a low battery
condition and ignores the delay to
report the condition if necessary. A
restoral is sent when the input is
deactivated.
Low Battery: When activated, the
D9068 sends a Low Battery Report. A
restoral is sent when the input is
deactivated.
40
The AC Fail Delay time set for
the FACP is independent of the
AC Fail Delay time set for the
D9068. If you program the FACP
for an AC Fail Delay time and
then program the D9068 for an
AC Fail Delay time, the AC
Fail Delay times are combined.
For example, if the FACP AC
Fail Delay time is set for 6 h
and the D9068 AC Fail Delay
time is set for 12 h, the AC
Fail Report is sent from the
D9068 18 hours after the AC
failure.
All inputs are non-latching. A
restoral is sent when the input
is deactivated.
For fail-safe operation,
program the system fault input
to Fault on Open.
To view specific active events,
connect the D7033/FMR-DACT-
KEYPAD Keypad Programmer and
press [1] for Status.
Refer to Appendix C: Fire
Communicator Report Summary on
page 56 for the specific
messages sent for each event.
To set an input option:
1. At the Prog Inputs submenu, enter the
point number you want to program and
press [1] for CONFIGURE. The window
shows [# Command]. The display
scrolls through the PROG INPUT
options.
2. Press [1] to select FIRE.
ACTVTN TYPE (___)
1: FIRE
2: WATERFLOW
3: SUPERVISORY
4: MONITOR
5: SYS FAULT
6: AC FAILURE
7: LOW BATTERY
Bosch Security Systems, Inc. | 3/13 | F01U071094-07
FAULT ON (____)
1: FAULT ON SHORT
2: FAULT ON OPEN