Address Setup

14

Chack at Main Power-on

After turning on the main power of the indoor units and outdoor unit in the refrigerant line to conduct a test opera-
tion, check the following items in each outdoor and indoor unit.
(After turning on the main power, be sure to check in order: indoor unit
<Check on the outdoor unit>
(1) Check that all the rotary switches, SW01, SW02, and SW03, on the interface PC board of the header unit are
set to "1."
(2) If another check code is displayed on the 7-segment display [B], remove the cause of the problem referring to
Section, "TROUBLESHOOTING".
(3) Check that "L08" is displayed on the 7-segment display [B] on the interface PC board of the header unit.
(L08: Indoor address not set up)
(If the address setup operation has already been completed during servicing, etc., the above check code is not
displayed, and "U1" is displayed on the 7-segment display [A].)
Interface PC board
<Check on the indoor unit>
(1) Display check on the remote controller (in the case of a wired remote controller)
Check that a frame, as shown in the following figure at left, is displayed on the LC display section of the remote
controller.
Correct
Normal status
(power supplied and operation stopped)
If no frame is displayed, as shown in the above figure at right, the remote controller does not have a normal
supply of power; check the following items.
• Check the power supply of the indoor unit.
• Check the cabling between the indoor unit and the remote controller.
• Check whether there is a cutoff of wire around the indoor control PC board or not, and check for connection
failures of the connectors.
• Check for failure of the transformer for the indoor electrical control box.
• Check for failure of the indoor control PC board.
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
FILTER
RESET
TEST
SET
CL
SWING/FIX
UNIT LOUVER
SW04
Push switches
D600 D601 D602 D603 D604
7-segment display
[A]
SW01 SW02 SW03
Rotary switches
Incorrect
outdoor unit.)
SW05
SW15
7-segment display
[B]
TEMP.
ON / OFF
TIMER SET
FAN
TIME
SAVE
FILTER
RESET
TEST
SET
CL
SWING/FIX
When power is not supplied normally
MODE
VENT
UNIT LOUVER

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents