Refrigerant Piping
2
Additional refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of
refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
additional refrigerant.
Outdoor unit type
Charged amount (kg)
Cooling only model
Outdoor unit type
Charged amount (kg)
Additional refrigerant charge amount at site = [1] + [2] + [3]
[1]. Compensation by system HP (Table 1)
[2]. Additional refrigerant charge amount Indoor unit (Table 2)
[3]. (Real length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 m (Table 3)) × 1.2
For HT8P - E model
Table 1
Standard model
High efficiency
model
MAP080 MAP100 MAP120 MAP140 MAP160 MAP180 MAP200 MAP220
MAP080 MAP100 MAP120 MAP140 MAP160 MAP180 MAP200 MAP220
1
0
5 .
Combination
System
HP
HP
8
8
–
10
10
–
12
12
–
14
14
–
16
16
–
18
18
–
20
20
–
22
22
–
24
12
12
26
14
12
28
16
12
30
16
14
32
16
16
34
18
16
36
20
16
38
22
16
40
20
20
42
22
20
44
22
22
46
16
16
48
16
16
50
18
16
52
20
16
54
22
16
56
20
20
58
22
20
60
22
22
20
10
10
22
12
10
36
12
12
38
14
12
40
14
14
42
14
14
44
16
14
54
20
20
<Cooling,Heat pump type>
11.5
Charged
refrigerant (kg)
–
11.5
–
11.5
–
11.5
–
11.5
–
11.5
–
11.5
–
11.5
–
11.5
–
23
–
23
–
23
–
23
–
23
–
23
–
23
–
23
–
23
–
23
–
23
14
34.5
16
34.5
16
34.5
16
34.5
16
34.5
16
34.5
16
34.5
16
34.5
–
23
–
23
12
34.5
12
34.5
12
34.5
14
34.5
14
34.5
14
34.5
1 1
5 .
Compensation by
System HP
kg
-3.5
-3.5
-1.5
-1.0
-0.5
1.5
1.5
1.5
-3.0
-2.5
-2.0
-1.5
-1.0
1.0
1.0
1.0
3.0
3.0
3.0
-6.5
-6.5
-0.5
-0.5
-0.5
2.5
2.5
2.5
-7.0
-7.0
-12.5
-10.5
-8.5
-4.5
-4.5
1.5