Outdoor Interface P.C board

Outdoor Interface P.C. board Function Setting

Swithch / Function Setting Exchange

Part type
bit 1 Compressor 1 backup
bit 2 Compressor 2 backup
SW06
DIP SW 4 bit
All bit1 and 2 are ON: Setup of outdoor unit backup
bit 1 Demand control 1
SW07
DIP SW 4 bit
bit 2 Demand control 2 (Expansion function)
In case of header outdoor unit
bit 2 Indoor connection capacity over
bit 4 Judgment of error for No. of connected
SW09
DIP SW 4 bit
In case of terminal outdoor unit
bit 4 Exchange of Outdoor unit No. / Start
bit 2 Outdoor fan high static pressure
bit 3 For low noise operation
SW10
DIP SW 4 bit
bit 4
bit 4 Operation switching when indoor water
SW11
DIP SW 4 bit
bit 1 Selection of PMV open/close or
bit 2
SW12
DIP SW 4 bit
SW13
DIP SW 4 bit
bit 4 Line address setup
bit 1 Line address setup
bit 2
SW14
DIP SW 4 bit
bit 3
bit 4
bit 1 Option function
bit 2
SW16
DIP SW 4 bit
bit 1 Communication termination resistance
SW30
DIP SW 2 bit
bit 2 Communication termination resistance
Manual full opening operation for PMV
CN30 Check connector
opening operation
Manual full closing operation for PMV
CN31 Check connector
opening operation
*1 PMV full open/full close operation by short-circuited CN30/CN31 is for PMV which was selected by setting
of SW12.
(Standard specifications)
Exchange of upper limit regulation
Exchange of 2 steps to 4 steps of
upper limit
Judgment of error
indoor units
order No.
operation
overflow error detected
manual operation
bit 1 bit 2
OFF OFF
O
N OFF
OFF ON
Output exchange of external output
P.C. boa
bit 1 bit 2
OFF OFF Compressor operation output
ON OFF
between outdoor units
between indoor and outdoor units
Exchange contents
OFF: Normal, ON: Backup when compressor 1
was in trouble
OFF: Normal, ON: Backup when compressor 2
was in trouble
OFF: 0 to 100%
ON : Middle to 100%
OFF: 2 steps (Standard)
ON : 4 steps
OFF: Check code judgment
ON : None (when backup setting for outdoor unit)
OFF: No check code judgment
ON : Check code judgment
OFF: Outdoor unit No. [U. #] (#: 1 to 3)
ON : Outdoor start order No. [y. #] (#: 1 to 3)
OFF: Normal
ON : High static pressure operation
OFF: Normal
ON : INV frequency upper limit restriction
OFF: Normal
ON : Fan rpm upper limit restriction
OFF: Entire system stops
ON : System operation continues
(Room which trouble occurred only stops.)
(According to the following setting contents)
PMV1 opens/closes by operation of CN30/CN31 (*1)
PMV3 opens/closes by operation of CN30/CN31 (*1)
Heat Recovery Not use
PMV4 opens/closes by operation of CN30/CN31 (*1)
(Used by combining with SW14)
(According to the following setting contents)
Display of system operation ratio
OFF: No termination resistance
ON : With termination resistance
OFF: No termination resistance
ON : With termination resistance
When released: Normal,
When short-circuited: Open fully (2 minutes)
When released: Normal,
When short-circuited: Closed fully (2 minutes)
65
Initial setting
at shipment
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
Released
Released