Address Setup
26
To change all the indoor unit addresses using an arbitrary wired remote controller.
(The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
NOTE
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check/change mode and change the addresses.
- - --
SET
DATA
TEMP.
1
FILTER
RESET TEST
3
Cancels the line selection
If no number appears on UNIT No., no outdoor unit exists on the line. Push
2
following step
.
(Execute it while the units are stopped.)
1
Push and hold the TIME
At first, the line 1 and CODE No.
2
UNIT LOUVER
Push
(left side of the button) and
3
SET
Push the
button.
• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD
display and the fan and louvers of the unit are activated.
At first, the current indoor unit address is displayed in SET DATA.
(No system address is indicated.)
4
Push the TIME
Change the value in SET DATA to that of a new address.
5
SET
Push the
button to confirm the new address on SET DATA.
6
UNIT LOUVER
Push the
Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after
another. Only the fan and louvers of the selected indoor unit are activated.
4
Repeat steps
7
SET
Push the
button.
(All the segments on the LCD display light up.)
8
TEST
Push the
button to finish the procedure.
CODE No.
SETTING
UNIT No.
R.C.
No.
ON / OFF
TIMER SET
TIME
SET
CL
TEST
/
and
(Address Change) are indicated on the LCD display.
/
buttons repeatedly to change the value of the indoor unit address in SET DATA.
button (left side of the button) repeatedly to select another address to change.
6
to
to change the indoor unit addresses so as to make each of them unique.
4
8
2
Finish
buttons at the same time for more than 4 seconds.
SWING/FIX
buttons repeatedly to select a system address.
CODE No.
SET
DATA
SETTING
UNIT No.
R.C.
No.
TEMP.
ON / OFF
TIMER SET
TIME
FILTER
RESET TEST
SET
CL
5, 7
Push to finish
setting.
CL
button and select another line
6