Remote Controller Distinction Function; Distinction Procedure - Toshiba SMMS-e Quick Reference

Eu model cooling type heat pump type
Hide thumbs Also See for SMMS-e:
Table of Contents

Advertisement

Service Support
Function

Remote Controller Distinction Function

This function is provided to distinguish the remote controller connected to the indoor unit from the outdoor unit for a
refrigerant circuit system by using switches on the interface P.C. board of the header unit.
<Distinction procedure>
Power ON
Set the display select switches on the
interface P.C. board of the header unit
as follows:
Set SW01/SW02/SW03 to [2/4/1]
Push the push switch SW04 on the
same board for 2 seconds or more.
"Checking" display of the connected
remote controller flashes.
Push the push switch SW05 on the
interface P.C. board of the header
unit for 2 seconds or more.
Interface P.C. board
<Check Code Clearing Function>
Be sure to turn on the power of the indoor unit
prior to the power of the outdoor unit.
7-segment display
[A]
[B]
[
] [
]
A 1
7-segment display
[A]
[B]
[
] [
]
A 1
FF
Check the connected remote controller
End
Other end conditions:
1. 10 minutes has passed
2. SW01, SW02, or SW03 changed to other position.
7-segment display [A]
SW04
SW01
<Rotary switches>
Operation
7-segment display [B]
SW05
SW02
SW03