System Restriction - Toshiba SMMS-e Quick Reference

Eu model cooling type heat pump type
Hide thumbs Also See for SMMS-e:
Table of Contents

Advertisement

Refrigerant Piping
4
For HT8P - E
Allowable length of refrigerant pipes and allowable height difference between units
Height
difference
between
outdoor
units
H3 ≤ 5 m
Height
difference
between
outdoor
and indoor
units:
H1 ≤ 70 m
First branching
section

System restriction

O
u
d t
o
r o
u
n
t i
c
o
m
b
n i
T
t o
l a
c
a
p
a
i c
y t
f o
o
u
n I
d
o
r o
u
n
t i
c
o
n
n
e
t c
Total capacity of indoor units
(varies depending on the height difference between
indoor units.)
Note
(*1):(D) is outdoor unit furthest from the 1st branch and (j) is the indoor unit furthest from the 1st branch.
(*2) :If the height difference (H1) between indoor and outdoor unit exceeds 3 m, set 65 m or less.
(*3) :If the max. combined outdoor unit capacity is 54HP or more, then max. equivalent length is 70 m or less (real length is 50 m or less).
(*4) :If the height difference (H2) between indoor units exceeds 3 m, set 50 m or less.
utdoor unit
A
B
Header
Follower
unit
unit
La
Lb
LA
Outdoor unit connection piping kit
(For linking of outdoor units)
The longest piping between outdoor units:
LO ≤ 25 m
L3
The longest piping length from the first branch: Li ≤ 90 m
Y-shaped
branching joint
f
t a
o i
n
d t
o
r o
u
i n
s t
o i
n
<Cooling,Heat pump type>
C
Follower unit
Lc
Branching header
Indoor unit connecting
pipe
Indoor unit
a
b
The longest piping length: L ≤ 235 m
L5
L4
h
g
Indoor unit
U
U
U
p
H2 ≤ 15m
135% of outdoor units' capacity
15m < H2
105% of outdoor units' capacity
Y-shaped branching
L7
joint
c
d
e
L6
i
j
(j)
p
o t
3
u
i n
s t
p
o t
6
0
H
P
o t
6
4
u
i n
s t
Height
difference
between
indoor
units:
H2 ≤ 40 m

Hide quick links: