Toshiba RAV-SM562BT-E Installation Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM562BT-E:

Advertisement

AIR CONDITIONER
CLIMATISEUR
(TYPE SPLIT)
KLIMAGERÄT
(SPLIT-TYP)
CONDIZIONATORE D'ARIA
AIRE ACONDICIONADO
AR CONDICIONADO
AIRCONDITIONER
ÊËÉÌÁÔÉÓÔÉÊÏ
<Concealed Duct Type>/<Type à conduits dissimulés>
<Lüftungskanalmontage in der Zwischendecke>/<Tipo a condotto nascosto>
<Modelo con conductos ocultos>/<Tipo conduta embutida>
<Type met weggewerkte kanalen>/<Ôýðïò óõãêåêáëõììÝíïõ áãùãïý>
Heat Pump Model/Modèle à thermopompe
Geräte mit Heizung/Modello con pompa di riscaldamento
Modelo con bomba de calor/Modelo de bomba térmica
Model met warmtepomp/ÌïíôÝëï ìå Áíôëßá Èåñìüôçôáò
Indoor Unit/Unité intérieure
Raumeinheit/Unità interna
Unidad interior/Unidade interior
Binnenunit/ÅóùôåñéêÞ mïíÜäá
RAV-SM562BT-E
RAV-SM802BT-E
RAV-SM1102BT-E
RAV-SM1402BT-E
Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the indoor unit.
• For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
Veuillez lire attentivement ce Manuel d'installation avant d'installer le climatiseur.
• Ce manuel décrit la procédure d'installation de l'unité intérieure.
• Pour installer l'unité extérieure, reportez-vous au Manuel d'installation fourni avec l'unité extérieure.
Bitte lesen Sie dieses Handbuch sorgfältig, bevor Sie mit der Installation des Klimagerätes beginnen.
• In diesem Handbuch wird die Installation der Raumeinheit beschrieben.
• Um die Außeneinheit zu installieren, folgen Sie den Anweisungen in dem Handbuch, das der
Außeneinheit beiliegt.
Prima di installare il condizionatore d'aria, leggere con attenzione questo manuale d'installazione.
• Questo manuale descrive il metodo d'installazione dell'unità interna.
• Per l'installazione dell'unità esterna, fare riferimento al manuale d'installazione fornito insieme all'unità esterna.
Lea atentamente este Manual de instalación antes de proceder a la instalación del aparato de aire acondicionado.
• Este manual describe el método de instalación de la unidad interior.
• Para la instalación de la unidad exterior, consulte el Manual de instalación que acompaña a la unidad exterior.
Leia atentamente o presente Manual de Instalação antes de instalar o Ar Condicionado.
• O presente manual descreve o método de instalar a unidade interior.
• Para a instalação de uma unidade exterior, siga o Manual de Instalação que acompanha a unidade exterior.
Lees deze installatiehandleiding zorgvuldig door voordat u de airconditioner gaat installeren.
• Deze installatiemethode beschrijft de installatiemethode van de binnenunit.
• Zie voor de installatie van de buitenunit, de installatiehandleiding bij de buitenunit.
Ðáñáêáëþ äéáâÜóôå ðñïóå÷ôéêÜ ôï Åã÷åéñßäéï ÅãêáôÜóôáóçò ðñéí áðü ôçí åãêáôÜóôáóç ôïõ Êëéìáôéóôéêïý.
• Ôï ðáñüí Åã÷åéñßäéï ðåñéãñÜöåé ôç ìÝèïäï åãêáôÜóôáóçò ôçò åóùôåñéêÞò ìïíÜäáò.
• Ãéá ôçí åãêáôÜóôáóç ôçò åîùôåñéêÞò ìïíÜäáò, áêïëïõèÞóôå ôï Åã÷åéñßäéï ÅãêáôÜóôáóçò ðïõ óõíïäåýåé ôçí
åîùôåñéêÞ ìïíÜäá.
(SPLIT TYPE)
(TIPO SPLIT)
(TIPO SPLIT)
(TIPO SPLIT)
(GESPLITST TYPE)
(ÔÕÐÏÓ SPLIT)
Outdoor Unit/Unité extérieure
Außengerät/Unità esterna
Unidad exterior/Unidade exterior
Buitenunit/ÅîùôåñéêÞ mïíÜäá
RAV-SM562AT-E
RAV-SM802AT-E
RAV-SM1102AT-E
RAV-SM1402AT-E
INSTALLATION MANUAL
MANUEL D’INSTALLATION
INSTALLATIONS-HANDBUCH
MANUALE D’INSTALLAZIONE
MANUAL DE INSTALACIÓN
MANUAL DE INSTALAÇÃO
INSTALLATIEHANDLEIDING
ÅÃ×ÅÉÑÉÄÉÏ ÅÃÊÁÔÁÓÔÁÓÇÓ
SP562AT-E
SP802AT-E
SP1102AT-E
SP1402AT-E

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-SM562BT-E

  • Page 1 Modelo con bomba de calor/Modelo de bomba térmica Model met warmtepomp/ÌïíôÝëï ìå Áíôëßá Èåñìüôçôáò Indoor Unit/Unité intérieure Outdoor Unit/Unité extérieure Raumeinheit/Unità interna Außengerät/Unità esterna Unidad interior/Unidade interior Unidad exterior/Unidade exterior Binnenunit/ÅóùôåñéêÞ mïíÜäá Buitenunit/ÅîùôåñéêÞ mïíÜäá RAV-SM562BT-E RAV-SM562AT-E SP562AT-E RAV-SM802BT-E RAV-SM802AT-E SP802AT-E RAV-SM1102BT-E RAV-SM1102AT-E SP1102AT-E RAV-SM1402BT-E...
  • Page 2 ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refriger- ant R22 in order to prevent destruction of the ozone layer. UTILISATION DU NOUVEAU REFRIGERANT Ce climatiseur est d’un type inédit qui utilise le nouveau réfrigérant HFC (R410A) au lieu du réfrigérant traditionnel R22, afin d’éviter la destruction de la couche d’ozone.
  • Page 3 CONTENTS Accessory parts and Parts to be procured locally ..... 1 ELECTRICAL WORK ............18 PRECAUTIONS FOR SAFETY ..........2 TEST RUN ................20 SELECTION OF INSTALLATION PLACE ......4 TROUBLESHOOTING ............21 INSTALLATION OF INDOOR UNIT ........5 Applicable Controls ............. 22 AIR DUCTING WORK .............
  • Page 4: Accessory Parts And Parts To Be Procured Locally

    Accessory parts and Parts to be procured locally r Accessory parts Part name Q’ty Shape Part name Q’ty Shape 562BT Pipe insulator Clamp screw 802BT 1102BT 1402BT (with pedestal) 562BT Connecting cable for Clamp for air High static pressure tap 802BT filter fixing 1102BT...
  • Page 5: Precautions For Safety

    PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. • After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
  • Page 6 PRECAUTIONS FOR SAFETY • After unpacking the unit, examine it carefully if there are possible damage. • Do not install in a place that might increase the vibration of the unit. • To avoid personal injury (with sharp edges), be careful when handling parts. •...
  • Page 7: Selection Of Installation Place

    SELECTION OF INSTALLATION PLACE WARNING • Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. • Install the air conditioner at a height 2.5m or more from the floor. If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you may contact with revolving fan or active electricity.
  • Page 8: Installation Of Indoor Unit

    INSTALLATION OF INDOOR UNIT WARNING Install the air conditioner certainly at a place to sufficiently withstand the weight. If the strength is insufficient, the unit may fall down resulting in human injury. Perform a specified installation work to guard against an earthquake. An incomplete installation can cause accidents by the units falling and dropping.
  • Page 9: External View

    External view REQUIREMENT The hanging bolt pitch on horizontal direction (B) is not halved at center with the ceiling opening size. Therefore, check the relational position in the following figure. Drain pipe connecting port Refrigerant pipe for vinyl chloride pipe Discharge port flange connecting port N-Ø200...
  • Page 10 INSTALLATION OF INDOOR UNIT 1. Hanging down of indoor unit Hanging bolt Refer to installation figures of hanging material and M10 flat washer (W3/8 or M10) (Accessory) hanging bolt. • Adjustment of hanging bolt length and nut (W3/8 or M10) position M10 flat washer (Accessory)
  • Page 11: Concealed Duct Type

    Supply chamber Concealed duct type Channel Supply grille Supplying 200mm (diam.) round duct Supplying Indoor unit Returning Return air grille NOTE: • Recommended supplying grille size 400 cm² each or more Ledge ceiling concealed duct type Supplying Supply grille Indoor unit Supply chamber Supplying...
  • Page 12: Air Ducting Work

    AIR DUCTING WORK Static pressure characteristics of each model Fig. 1 RAV-SM562BT (Round duct) Fig. 3 RAV-SM802BT (Round duct) Standard air volume 780m³/h Standard air volume 1140m³/h 1000 1140 1200 1300 Air volume m³/h Air volume m³/h Fig. 2 RAV-SM562BT (Square duct) Fig.
  • Page 13 Fig. 5 RAV-SM1102BT (Round duct) Fig. 7 RAV-SM1402BT (Round duct) Standard air volume 1620m³/h Standard air volume 1980m³/h 1620 1980 1200 2000 1200 1800 2200 2400 Air volume m³/h Air volume m³/h Fig. 6 RAV-SM1102BT (Square duct) Fig. 8 RAV-SM1402BT (Square duct) Standard air volume 1620m³/h Standard air volume 1980m³/h 1620...
  • Page 14 AIR DUCTING WORK Installation reference (Example for RAV-SM802BT model) The air supply ducting work is classified in two ways, one is branched by the round ducts, and the other is branched by the square ducts. (Be sure to divide the air supply duct into three or more branches.) <Round duct>...
  • Page 15 <Square duct> Connecting method of the duct 1. Using 6 screws, mount the flange to the supply air port of the indoor unit. (Fig. 2) 1. Supply air side 2. Make the square duct according to inner dimension <Round duct> of the flange A x 1.
  • Page 16 AIR DUCTING WORK Hanging of indoor unit Lift up the unit with a lifter, etc., and set the hanging metal in the hanging bolt. • Hook nut of the hanging bolt to the groove of the hanging metal on Washer Hanging bracket the main unit.
  • Page 17: Drain Piping Work

    DRAIN PIPING WORK Piping material 1.5m to 2m Support • For laying pipes underground, use hard vinyl Indoor bracket chloride pipe. VP25 (Inner diamater Ø32mm) unit 1/100 or more Thermal downward slope insulator Arched shape Piping and cautions NO GOOD •...
  • Page 18 DRAIN PIPING WORK Drain-up If down-slope cannot be set on a drain pipe, drain-up is possible. • Set the height of drain pipe 550mm or less from the bottom face of the indoor unit. • Pull out the drain pipe from connecting port of the drain pipe of the indoor unit by 100mm or shorter, and stand up it 100mm or shorter...
  • Page 19: Refrigerant Piping And Evacuating

    REFRIGERANT PIPING AND EVACUATING • Flaring dia meter size : A (Unit : mm) Refrigerant piping 1. If the outdoor units are to be mounted on a wall, - 0.4 Outer diam. of copper pipe make sure that the supporting platform is R410A sufficiently strong.
  • Page 20: Air Purge

    REFRIGERANT PIPING AND EVACUATING Piping with outdoor unit Open the valve fully • Shape of valve differs according to the outdoor unit. Open the valve of the outdoor unit fully. A 4mm- hexagonal wrench is required for opening the valve. For details of installation, refer to the Installation Manual of the outdoor unit.
  • Page 21: Electrical Work

    ELECTRICAL WORK NOTE: For selection and connection method of the power supply cords, refer to the details in the Installation Manual of the outdoor unit. CAUTIONS • Be sure connect earth wire. Do not connect the earth wire to gas pipe, pipe of water supply, lightning conductor, and earth wire of telephone.
  • Page 22: Wiring Diagram

    ELECTRICAL WORK Cabling Remote controller cabling  1. As shown in the figure, remove a screw • Strip approx. 9mm the cable to be connected. then remove cover of the electric part. • Non polarity, 2 core cable is used for cabling of the 2.
  • Page 23: Test Run

    TEST RUN Before test run • Before turning on the power supply, carry out the following procedure. 1) Using 500V-megger, check 1MΩ or more exists between the terminal block 1 to 3 and the earth. If 1MΩ or less is detected, do not run the unit. Do not apply to the remote controller circuit. 2) Check the valve of the outdoor unit being opened fully.
  • Page 24: Troubleshooting

    TROUBLESHOOTING Confirmation and check When a trouble occurred in the air conditioner, the CODE No. check code and the indoor unit No. appear on the UNIT No. display part of the remote controller. R.C. The check code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following “Confirmation of error Check code...
  • Page 25: Contents

    APPLICABLE CONTROLS NOTIFICATION When using the equipment at the first time, it will take a lot of time that the remote controller accepts an operation after power was on. However, it is not a trouble. • Automatic address • While automatic addressing, the operation cannot be performed on the remote controller. •...
  • Page 26: Applicable Controls

    APPLICABLE CONTROLS Setup of external static pressure Matching with the resistance (External static pressure) of the duct to be connected, be sure to set up the tap → → → → → exchange according to the basic operation procedure ( •...
  • Page 27: Check And Test Operation

    Change of lighting time of filter sign To secure better effect of heating According to the installation condition, the lighting time When it is difficult to obtain satisfactory heating due to of the filter sign (Notification of filter cleaning) can be installation place of the indoor unit or structure of the changed.
  • Page 28: Group Control

    APPLICABLE CONTROLS Group control Simultaneous twin system If combining with an outdoor unit, ON/OFF operation of two <Twin system> indoor units is simultaneously available for the twin system. Outdoor unit Indoor unit Indoor unit • For wiring procedure and wiring method, follow to the Remote controller “Electric work”...
  • Page 29  Procedure example Manual address setup procedure While the operation stops, change the setup. (Be sure to stop the operation of the unit.) CODE No. DATA SETTING TEST UNIT No. R.C. TEMP. ON / OFF TIMER SET MODE TIME SWING/FIX VENT FILTER RESET TEST...
  • Page 30 APPLICABLE CONTROLS Procedure Description If there is other indoor unit to be changed, repeat Indoor unit No. before setup change is displayed. procedure to change the setup. UNIT CODE No. When the above setup has finished, push DATA SETTING TEST select the indoor unit No.
  • Page 31: Installation/Servicing Tools

    INSTALLATION/SERVICING TOOLS Tools Tools Applicable to R22 model Tools Applicable to R22 model ¡ Gauge manifold Flare tool (clutch type) Charge hose Gauge for projection — —— adjustment ¡ Vacuum pump ¡ Electronic balance for adapter refrigerant charging Torque wrench (nominal diam.
  • Page 32 This product is compliant with Directive 2002/95/EC, and cannot be disposed as unsorted municipal waste. Ce produit est conforme à la Directive 2002/95/CE et il ne peut pas être jeté avec les ordures ménagères non triées. Dieses Produkt entspricht der Richtlinie 2002/95/EWG und darf nicht als normaler, unsortierter Hausabfall entsorgt werden.