5-12
Using the High-Speed Counter
Publication 1762-RM001C-EN-P
High Preset Reached (HPR)
Description
Address
HPR - High
HSC:0/HPR bit
Preset Reached
(1) For Mode descriptions, see HSC Mode (MOD) on page 5-16.
The HPR (High Preset Reached) status flag is set (1) by the HSC
sub-system whenever the accumulated value (HSC:0.ACC) is greater than
or equal to the high preset variable (HSC:0.HIP).
This bit is updated continuously by the HSC sub-system whenever the
controller is in an executing mode.
Underflow (UF)
Description
Address
UF - Underflow HSC:0/UF bit
(1) For Mode descriptions, see HSC Mode (MOD) on page 5-16.
The UF (Underflow) status flag is set (1) by the HSC sub-system whenever
the accumulated value (HSC:0.ACC) has counted through the underflow
variable (HSC:0.UNF).
This bit is transitional and is set by the HSC sub-system. It is up to the
control program to utilize, track if necessary, and clear (0) the underflow
condition.
Underflow conditions do not generate a controller fault.
Underflow Mask (UFM)
Description Address
UFM -
HSC:0/UFM bit
Underflow
Mask
(1) For Mode descriptions, see HSC Mode (MOD) on page 5-16.
The UFM (Underflow Mask) control bit is used to enable (allow) or
disable (not allow) a underflow interrupt from occurring. If this bit is clear
(0), and a Underflow Reached condition is detected by the HSC, the HSC
user interrupt is not executed.
This bit is controlled by the user program and retains its value through a
power cycle. It is up to the user program to set and clear this bit.
Data Format HSC Modes
(1)
2 to 7
Data Format HSC Modes
(1)
0 to 7
Data Format HSC Modes
2 to 7
Type
User Program Access
status read only
Type
User Program Access
status read/write
(1)
Type
User Program Access
control read/write