6-22
Using High-Speed Outputs
Publication 1762-RM001C-EN-P
PWM Profile Parameter Select (PP)
Element Description
PP - Profile Parameter Select
The PWM PP (Profile Parameter Select) selects which component of the
waveform is modified during a ramp phase:
• Set (1) - selects Frequency
• Cleared (0) - selects Duty Cycle
The PWM PP bit cannot be modified while the PWM output is running/
enabled. See PWM ADD on page 6-25 for more information.
PWM Idle Status (IS)
Element Description Address
IS - PWM Idle Status
PWM:0/IS bit
The PWM IS (Idle Status) is controlled by the PWM sub-system and
represents no PWM activity. It can be used in the control program by an
input instruction.
• Set (1) - PWM sub-system is in an idle state.
• Cleared (0) - PWM sub-system is not in an idle state (it is running).
PWM Error Detected (ED)
Element Description
ED - PWM Error Detection
The PWM ED (Error Detected) bit is controlled by the PWM sub-system. It
can be used by an input instruction on any rung within the control
program to detect when the PWM instruction is in an error state. If an
error state is detected, the specific error is identified in the error code
register (PWM:0.ED).
• Set (1) - Whenever a PWM instruction is in an error state.
• Cleared (0) - Whenever a PWM instruction is not in an error state.
Address
Data Format Range Type
PWM:0/PP bit
Data Format Range
0 or 1
Address
Data
Range
Format
PWM:0/ED bit
0 or 1
User Program
Access
0 or 1
control read/write
Type
User Program
Access
status read only
Type
User Program
Access
status read only