Table 6.3 Pulse Train Output Error Codes
Error
Non-User
Recoverable
Code
Fault
Fault
-2
Yes
No
-1
Yes
No
0
---
---
1
No
No
2
No
No
3
No
Yes
4
No
Yes
5
No
No
6
No
Yes
7
No
Yes
PTO Error Code (ER)
Sub-Element
Address
Description
ER - Error Code
PTO:0.ER
PTO ER (Error Codes) detected by the PTO sub-system are displayed in
this register. The error codes are shown in the table below:
Instruction
Error
Description
Errors
Name
No
Overlap
An output overlap is detected. Multiple functions are assigned to the same
Error
physical output. This is a configuration error. The controller faults and the
User Fault Routine does not execute. Example: PTO0 and PTO1 are both
attempting to use a single output.
No
Output
An invalid output has been specified. Output 2 and output 3 are the only valid
Error
choices. This is a configuration error. The controller faults and the User Fault
Routine does not execute.
Normal
Normal (0 = no error present)
Yes
Hardstop
This error is generated whenever a hard stop is detected. This error does not
Detected
fault the controller.
To clear this error, scan the PTO instruction on a false rung and reset the EH
(Enable Hard Stop) bit to 0.
Yes
Output
The configured PTO output (2 or 3) is currently forced. The forced condition
Forced
must be removed for the PTO to operate.
Error
This error does not fault the controller. It is automatically cleared when the
force condition is removed.
No
Frequency
The operating frequency value (OFS) is less than 0 or greater than 20,000.
Error
This error faults the controller. It can be cleared by logic within the User Fault
Routine.
No
Accel/
The accelerate/decelerate parameters (ADP) are:
• less than zero
Decel
Error
• greater than half the total output pulses to be generated (TOP)
• Accel/Decel exceeds limit (See page 6-13.)
This error faults the controller. It can be cleared by logic within the User Fault
Routine.
Yes
Jog Error PTO is in the idle state and two or more of the following are set:
• Enable (EN) bit set
• Jog Pulse (JP) bit set
• Jog Continuous (JC) bit set
This error does not fault the controller. It is automatically cleared when the
error condition is removed.
No
Jog
The jog frequency (JF) value is less than 0 or greater than 20,000. This error
Frequency
faults the controller. It can be cleared by logic within the User Fault Routine.
Error
No
Length
The total output pulses to be generated (TOP) is less than zero. This error
Error
faults the controller. It can be cleared by logic within the User Fault Routine.
Data Format Range
word (INT)
-2 to 7
Using High-Speed Outputs
6-17
Type
User Program
Access
status
read only
Publication 1762-RM001C-EN-P