15-6
Sequencer Instructions
Word
B10:1
B10:2
B10:3
B10:4
B10:5
Publication 1762-RM001C-EN-P
If the position is equal to zero at start-up, when you switch the controller
from the program mode to the run mode, the instruction operation
depends on whether the rung is true or false on the first scan.
• If the rung is true, the instruction transfers the value in step zero.
• If the rung is false, the instruction waits for the first rung transition
from false-to-true and transfers the value in step one.
The bits mask data when reset (0) and pass data when set (1). The
instruction will not change the value in the destination word unless you
set mask bits.
The mask can be fixed or variable. It is fixed if you enter a hexadecimal
code. It is variable if you enter an element address or a file address (direct
or indirect) for changing the mask with each step.
The following figure indicates how the SQO instruction works.
Destination O:14.0
15
8 7
0000
0101
0000
1010
Mask Value 0F0F
15
8 7
0000
1111
0000
1111
Sequencer Output File #B10:1
0000
0000
0000
0000
1010
0010
1111
0101
1111
0101
0100
1010
0101
0101
0101
0101
0000
1111
0000
1111
SQO
SQO
Sequencer Output
EN
File
#B10:1
Mask
0F0F
DN
Dest
O14:0
Control
R6:20
Length
4<
Position
2<
External Outputs (O:14)
at Step 2
0
0
Step
0
1
2
Current Step
3
4
00
01
ON
02
03
ON
04
05
06
07
08
ON
09
10
ON
11
12
13
14
15