6-16
Using High-Speed Outputs
Publication 1762-RM001C-EN-P
PTO Jog Continuous (JC)
Sub-Element
Address
Description
JC - Jog Continuous
PTO:0/JC
The PTO JC (Jog Continuous) bit instructs the PTO sub-system to generate
continuous pulses. The frequency generated is defined by the Jog
Frequency parameter in the PTO function file. Jog Continuous operation
is only possible under the following conditions:
• PTO sub-system in idle
• Jog Pulse not active
• Enable not active
The JC bit operates as follows:
• Set (1) - Instructs the PTO sub-system to generate continuous Jog
Pulses
• Cleared (0) - The PTO sub-system does not generate Jog Pulses
When the Jog Continuous bit is cleared, the current output pulse is
truncated.
PTO Jog Continuous Status (JCS)
Sub-Element Description Address
JCS - Jog Continuous Status PTO:0/JCS
The PTO JCS (Jog Continuous Status) bit is controlled by the PTO
sub-system. It can be used by an input instruction on any rung within the
control program to detect when the PTO is generating continuous Jog
Pulses. The JCS bit operates as follows:
• Set (1) - Whenever a PTO instruction is generating continuous Jog
Pulses
• Cleared (0) - Whenever a PTO instruction is not generating
continuous Jog Pulses.
Data Format
Range
bit
0 or 1
Data
Range
Format
bit
0 or 1
Type
User Program
Access
control read/write
Type
User Program
Access
status
read only