E-10
Protocol Configuration
Table E.5 Modbus to MicroLogix Memory Map - Detail
(MicroLogix 1200 Controllers and MicroLogix 1500 1764-LSP Series B and 1764-LRP Processors only)
Modbus Addressing Modbus Address Reference
0001 to 4096
Read/Write Modbus Coil Data space
10001 to 14096
Read Only Modbus Contact Data space
30001 to 30256
Read Modbus Input Register space
30501
Modbus Data Table Coil File Number
30502
Modbus Data Table Contact File Number
30503
Modbus Data Table Input Register File Number
30504
Modbus Data Table Holding Register File Number
30506
Pre-Send Delay
30507
Modbus Slave Address
30508
Inter-character Timeout
30509
RTS Send Delay
30510
RTS Off Delay
30511
Parity
30512
Presentation Layer Error Code
30512
Presentation Layer Error Code
30513
Presentation Layer Error Count
30514
Executed Function Code Error
30515
Last Transmitted Exception Code
30516
File Number of Error Request
30517
Element Number of Error Request
30518
Function Code 1 Message Counter - Read Single Output Coil
30519
Function Code 2 Message Counter - Read Discrete Input Image
30520
Function Code 3 Message Counter - Read Single Holding Register
30521
Function Code 4 Message Counter - Read Single Input Register
30522
Function Code 5 Message Counter - Set/Clear Single Output Coil
30523
Function Code 6 Message Counter - Read/Write Single Holding Register
30524
Function Code 8 Message Counter - Run Diagnostics
30525
Function Code 15 Message Counter - Set/Clear for Block of Output Coils
30526
Function Code 16 Message Counter - Read/Write for Block of Holding Registers
30527
Modem Status
30528
Total messages responded to by this slave
30529
Total messages to this Slave
30530
Total Messages Seen
30531
Link Layer Error Count
30532
Link Layer Error
31501 to 31566
Read Only System Status File
40001 to 40256
Read/Write Modbus Holding Register space.
41501 to 41566
Read/Write System Status File
Publication 1762-RM001C-EN-P
Modbus Function Code (decimal)
1, 5, 15
2
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
3, 6, 16
3, 6, 16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Micrologix 1500

Table of Contents