Clearing S:14 before executing the FRD instruction is shown below:
I:1
] [
0
When the input condition I:0/1 is set (1), a BCD value (transferred from a
4-digit thumbwheel switch for example) is moved from word N7:2 into
the math register. Status word S:14 is then cleared to make certain that
unwanted data is not present when the FRD instruction is executed.
MOV
MOVE
Source
N7:2
4660
Dest
S:13
4660
CLR
CLEAR
Dest
S:14
0
FRD
FROM BCD
Source
S:13
00001234
Dest
N7:0
1234
Conversion Instructions
11-7
0001 0010 0011 0100
S:13 and S:14 are
displayed in BCD format.
0000 0100 1101 0010