Functional Control
2.19
Pump Down Configuration at Compressor Stop
1
Introduction
Function
2
description
3
4
5
2–74
When the unit is switched off (local, remote, thermostat) the pump down procedure will be executed.
Pump down procedure:
■
request to shut down compressor
■
close electronic expansion valve
■
stop compressor or when one of the two conditions is met:
■
max time of pump down = 30 seconds
■
LP is below 1.2 bar
Pump Down Config
Enable
Max time
Min Press.
30 s
1.2 bar
ESIE07-05
Part 2 – Functional Description