Daikin EWWQ-AJYNN Service Manual page 24

Water-cooled screw chillers
Table of Contents

Advertisement

ESIE07-05
1.4.5
Addressing of pLAN
To get the correct functionality of the pLAN net system, it is necessary to address correctly all the
installed components. Each component has a series of microswitches that must be set as specified in
the table below.
pLAN component
Local DISPLAY
Remote DISPLAY
(if available)
COMP. BOARD #1
COMP. BOARD #2
COMP. BOARD #3
COMP. BOARD #4
DRIVER EXV #1
DRIVER EXV #2
DRIVER EXV #3
DRIVER EXV #4
Part 2 – Functional Description
1
2
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
Microswitches
3
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
The Digital Controller
5
6
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2–13
1
2
3
4
5

Hide quick links: