Daikin EWWQ-AJYNN Service Manual page 82

Water-cooled screw chillers
Table of Contents

Advertisement

Functional Control
2.20.2
Transducer low pressure alarm
1
Function
description
2
3
4
5
2–76
LP
1.2
Setpoint
1.1
When the low pressure is below the LP setpoint (for the LP alarm delay time), the unit will go into
LP alarm.
When the low pressure alarm is activated and the LP rises above the LP setpoint + diff, it will be
possible to reset the transducer low pressure alarm.
When the low pressure sinks below the low pressure switch setpoint (0.6 bar), the unit will go into
alarm and a manual reset on the low pressure switch is needed.
ESIE07-05
If LP is below
possible
this value
to reset
LP Alarm
Time
Part 2 – Functional Description