ESIE07-05
Item description
Regulating Band
Dead Band
Max Pulldown Rate
StartUp DT
ShutDown DT
SoftLoad enable
Max Unit Load
Max Time
Limits for high chilled water start
Evaporator leaving temperature
Max Unit Load
Part 2 – Functional Description
Regul.
band
band
Neutral
Max Pull Down Rate
Startup
Dt
Shutdn
Dt
Softload
Enable
Enable
Softload
Maxstage
MaxTime
ChLWT
High
start
LWT
Max Comp. Stage
xx.x
˚C
xx.x
˚C
xx.x
˚C/min
xx.x
˚C
xx.x
˚C
N
Y
xxx
%
xxx
min
xx.x
˚C
xxx
%
The Digital Controller
Default
U.m.
3.0
°C
0.2
°C
1.2
°C/min
2.6
°C
1.7
°C
N
50
%
20
min
25
°C
70
%