ESIE07-05
2.7

Enable Soft Load

Function
The Soft load function can be enabled by keyboard in the user menu. The Soft load function limits the
description
unit load to a predetermined value (Max stage) for a set period (Max time). This function finds wide
application where the water temperature is high at the start up but without having a consistent thermal
load. This function allows energy saving during unit start up avoiding compressors useless loading.
Enable Soft Load
Enable Soft Load
Max stage
Max Time
Part 2 – Functional Description
Y
Y
50 %
20 min
Functional Control
1
2
3
4
5
2–59