The Digital Controller
1
2
3
4
5
2–36
Enable evaporator flow alarm
Enable condenser flow alarm
Evaporator flow alarm delay (if
enabled)
High discharge temperature setpoint
High pressure alarm setpoint
Low pressure alarm setpoint
Delay low pressure alarm
■
Ratio alarm setpoint
■
Min Load
■
Max Load
Delay pressure Ratio alarm
YES (MASTER); NO (SLAVES)
YES (MASTER); NO (SLAVES) Solo WHS
■
STARTUP DELAY = 20 s
■
OPERATING DELAY = 5 s
■
SETPOINT = 120 °C
■
DIFFERENTIAL = 5 °C
■
SETPOINT = 20.5 bar
■
DIFFERENTIAL = 05.0 bar
Transducers high
pressure alarm
Setpoint
Diff.
■
SETPOINT = 01.0 bar
■
DIFFERENTIAL = 00.5 bar
Transducers low
pressure alarm
Setpoint
Diff.
■
STARTUP DELAY = 120 s
■
OPERATING DELAY = 60 s
Low pressure alarm
delays
Startup delay
Run delay
1.4
1.8
Pressure ratio alarm
Min Load Setp
Max Load Setp
■
STARTUP DELAY = 180 s
■
OPERATING DELAY = 90 s
Pressure ratio alarm
Startup delay
Run delay
ESIE07-05
20.5
bar
05.0 bar
-01.0
bar
00.5 bar
120
s
060 s
1.4
1.8
180
s
090
s
Part 2 – Functional Description