Daikin EWWQ-AJYNN Service Manual page 42

Water-cooled screw chillers
Table of Contents

Advertisement

The Digital Controller
1
2
3
4
5
2–36
Enable evaporator flow alarm
Enable condenser flow alarm
Evaporator flow alarm delay (if
enabled)
High discharge temperature setpoint
High pressure alarm setpoint
Low pressure alarm setpoint
Delay low pressure alarm
Ratio alarm setpoint
Min Load
Max Load
Delay pressure Ratio alarm
YES (MASTER); NO (SLAVES)
YES (MASTER); NO (SLAVES) Solo WHS
STARTUP DELAY = 20 s
OPERATING DELAY = 5 s
SETPOINT = 120 °C
DIFFERENTIAL = 5 °C
SETPOINT = 20.5 bar
DIFFERENTIAL = 05.0 bar
Transducers high
pressure alarm
Setpoint
Diff.
SETPOINT = 01.0 bar
DIFFERENTIAL = 00.5 bar
Transducers low
pressure alarm
Setpoint
Diff.
STARTUP DELAY = 120 s
OPERATING DELAY = 60 s
Low pressure alarm
delays
Startup delay
Run delay
1.4
1.8
Pressure ratio alarm
Min Load Setp
Max Load Setp
STARTUP DELAY = 180 s
OPERATING DELAY = 90 s
Pressure ratio alarm
Startup delay
Run delay
ESIE07-05
20.5
bar
05.0 bar
-01.0
bar
00.5 bar
120
s
060 s
1.4
1.8
180
s
090
s