Procedure for Software Upload/Download
1.2
Copy from the Software Key to pCO²
1
3
3
4
5
3–4
2
Switch off the pCO
and remove the "expansion memory" cover with a screwdriver (see "Copy from
pCO² to the Software Key" on page 3–5/Fig. 1)
Set the key selector on
Insert the key in the corresponding pin connector as shown. (see "Copy from pCO² to the Software
Key" on page 3–5/Fig. 2)
Press simultaneously the buttons UP an DOWN then supply power to the pCO
Check the LED on the key is on (red color
Wait until the request of copying appears on the LCD display, then release the buttons and confirm
by pressing ENTER.
The data transfer operation takes about 50s using the 1MB key and 100s using the 2MB one.the
display will show a progressive series of numbers.
Once copied the application program starts, then switch off the pCO
cover in its place and switch on the pCO
2
Now the pCO
works with the program transferred by the key.
)
2
2
again,