ESIE07-05
2.9

Start Up With High Evaporator Water Temperature

Function
This function limits the load of each compressor to a set value (default 70%) until the outlet water
description
temperature is below the set value (default 25°C). This function helps the start up of the unit when the
water temperature is very high (35°C - 40°C) avoiding dangerous overheating of the motor and
disagreeable interventions for high pressure protection.
The value of maximum load of the compressors and the limit water temperature are modifiable under
the user menu.
High chLWT Start
LWT
Max Comp. Stage
Part 2 – Functional Description
25.0 ˚C
70 %
Functional Control
1
2
3
4
5