ESIE07-05
Delay low oil pressure alarm
Delay high oil pressure differential
Max differential oil pressure
Freeze protection
Liquid Injection
Evaporator heater
Supervisor configuration
Default parameter?
■
■
Password for driver configuration
Part 2 – Functional Description
Modem connection password
Password for driver configuration
(Exv manufacture)
■
STARTUP DELAY = 300 s
■
OPERATING DELAY = 90 s
Oil low pressure
alarm delays
Startup delay
Run delay
20 sec
Oil high pressure
diff. delays
Setp
Delay
2.5 bar
■
SETPOINT = 02.0 °C
■
DIFFERENTIAL = 01.0 °C
■
SETPOINT = 85.0 °C
■
DIFFERENTIAL = 10.0 °C
Liquid injection
Setpoint
Diff.
■
SETPOINT = 3.0 °C
■
DIFFERENTIAL = 1.0 °C
■
PROTOCOL = CAREL
■
COMMUNICATION SPEED = 19200
■
IDENTIFICATION NUMBER = 001
NO
0152
Reserved area
The Digital Controller
300
s
090
s
2.5
bar
020
s
085.0
˚C
10.0
˚C
2–37
1
2
3
4