Eaton 93PM Gen 2 150-1 Installation And Operation Manual
Eaton 93PM Gen 2 150-1 Installation And Operation Manual

Eaton 93PM Gen 2 150-1 Installation And Operation Manual

20–150 kw
Table of Contents

Advertisement

Quick Links

Eaton® 93PM Gen 2 UPS
20–150 kW (480V Three or Four-Wire) – 150 kW Frame
20–150 kW (480V Three or Four-Wire) – 150 kW Frame with Sidecar
(Top Wire Entry or Bypass)
Installation and Operation Manual
p/n: P-164001030
Revision 01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 93PM Gen 2 150-1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eaton 93PM Gen 2 150-1

  • Page 1 Eaton® 93PM Gen 2 UPS 20–150 kW (480V Three or Four-Wire) – 150 kW Frame 20–150 kW (480V Three or Four-Wire) – 150 kW Frame with Sidecar (Top Wire Entry or Bypass) Installation and Operation Manual p/n: P-164001030 Revision 01...
  • Page 2 National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ©Copyright 2025 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3 5.10 Third Party Intellectual Property Rights. The Firmware may contain components transfer the Firmware directly to a third party only in connection with the sale of the Eaton (including open source software components) that are owned by third parties (“Third Party product in which it is installed.
  • Page 4: Dear Customer

    Dear Customer, On behalf of everyone at Eaton, we thank you for partnering with us, for trusting us to maintain your business continuity and for preventing downtime at your facility. Our suite of backup power, power distribution and power management products are designed to protect you from a host...
  • Page 5 4 4 U U P P S S S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n ....................................................6 6 2 2 4.1 Preliminary Installation Information....................... 62 4.2 Unloading the UPS Cabinet from the Pallet..................... 62 4.3 Integrated Battery Cabinet Installation......................66 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 6 7.2.6 Display Menu Operation........................127 7.2.7 Sign In............................132 7.2.8 System Controls..........................134 7.3 Single UPS Operation ..........................138 7.3.1 Starting the UPS in Double Conversion Mode ..................138 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 7 1 1 0 0 P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s ................................................... . 1 1 5 5 5 5 10.1 Models ............................... 155 10.2 Specifications............................156 10.2.1 UPS Input............................156 10.2.2 UPS Output ........................... 156 10.2.3 UPS Environmental ......................... 157 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 8 1 1 1 1 W W a a r r r r a a n n t t y y ........................................................... . 1 1 5 5 8 8 viii Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 9 Four-Wire 100/150 kW UPS with SIAC-B (4-Breaker) Power Terminal Locations ........87 Figure 37. Four-Wire 150 kW UPS with SIAC-B (4-Breaker) Power Terminal Locations ..........88 Figure 38. RIB Terminal Detail........................89 Figure 39. Interface Terminal Locations......................92 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 10: Table Of Contents

    Eaton 93PM Gen 2 Three-Wire UPS System Oneline ................. 119 Figure 58. Eaton 93PM Gen 2 Three-Wire UPS with Top Entry Sidecar System Oneline .......... 120 Figure 59. Eaton 93PM Gen 2 Three-Wire UPS with Bypass Sidecar (SIAC-B) System Oneline........121 Figure 60.
  • Page 11 List of Figures Figure 81. REPO Operation ........................146 Figure 82. Optional Minislot Cards ....................... 147 Figure 83. Air Filter Location ........................152 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 12 Table 35. Display Menu Operation ....................... 127 Table 36. Controls Menu Operation ......................134 Table 37. Typical System Status Messages....................135 Table 38. IRC-MS Default Triggers ....................... 147 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 13 AC power to protect the customer's load from power failures. The Eaton 93PM Gen 2 UPS online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
  • Page 14 Introduction Figure 1. Eaton 93PM Gen 2 UPS Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 15 Introduction Figure 2. Eaton 93PM Gen 2 100/150 kW UPS with Sidecar UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 16 Alarm Contact – One alarm contact is provided for connection to equipment at the facility, such as a light, an audible alarm, or a computer terminal. The equipment connected to this contact alerts you to a UPS alarm. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 17 1 1 . . 1 1 . . 5 5 I I n n t t e e r r n n a a l l R R e e d d u u n n d d a a n n c c y y To deliver greater reliability, the Eaton 93PM Gen 2 UPS can be configured for internal redundancy. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM.
  • Page 18 The cabinets match the UPS cabinet in style and color. The IAC-D may be installed on either the right or left side of the UPS cabinet. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 19 1 1 . . 2 2 . . 7 7 A A d d d d i i t t i i o o n n a a l l O O u u t t p p u u t t S S u u r r g g e e P P r r o o t t e e c c t t i i o o n n The Eaton 93PM Gen 2 UPS complies with ANSI 62.41 for line surges. However, if added security is required an additional Surge Protection Device (SPD) can be installed.
  • Page 20 U U s s i i n n g g T T h h i i s s M M a a n n u u a a l l This manual describes how to install and operate the Eaton 93PM Gen 2 UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation.
  • Page 21: Special Symbols

    Wire IAC-PD, 480V 4–Wire IAC-PD) Installation and Operation Manual for the following additional Phillips and Pozidriv are registered trademarks of Phillips Screw Company. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be information: Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates.
  • Page 22 1 1 . . 1 1 0 0 E E q q u u i i p p m m e e n n t t R R e e g g i i s s t t r r a a t t i i o o n n Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number: Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 23 ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors. Attempting to alter wiring can cause injury. • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 24: Safety Warnings

    à la terre si des charges y sont raccordées. • Ne pas ouvrir ni abîmer les batteries. L’électrolyte qu’elles contiennent est dangereux pour la peau et les yeux. Il peut être toxique. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 25 • Keep surroundings uncluttered, clean, and free from excess moisture. • Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 26 Maintenir les lieux rangés, propres et exempts d’une humidité excessive. • Respecter les étiquettes DANGER, MISE EN GARDE et AVERTISSEMENT se trouvant à l’intérieur et à l’extérieur de l’équipement. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 27: Warranty

    Warranty for details. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (a minimum two-week notice is required) to reserve a preferred startup date. 3 3 . . 1 1 C C r r e e a a t t i i n n g g a a n n I I n n s s t t a a l l l l a a t t i i o o n n P P l l a a n n Before installing the UPS system, read and understand how this manual applies to the system being installed.
  • Page 28 If the environment created by this microclimate exceeds the UPS operating specification, the UPS reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns for any servers that are exposed to them. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 29: Ups Installation Plan And Unpacking

    Des températures de fonctionnement supérieures à la plage recommandée entraîneront une diminution de la durée de vie et des performances de la batterie et pourront réduire ou annuler la garantie de la batterie. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 30: Table 2. Air Conditioning Or Ventilation Requirements During Full Load Operation

    The UPS equipment operating environment must meet the weight requirements shown in Table 3 and the size requirements shown in Figure 4 through Figure 11. Dimensions are in millimeters (inches). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 31: Table 3. Three-Wire Ups Cabinet Weights

    Eaton 93PM Gen 2 150–3 with empty Sidecar 542 (1194) 511 (1127) 6 at 85 (188) 567 (1250) 534 (1177) Eaton 93PM Gen 2 150–1 with 4-Breaker SIAC-B 6 at 89 (196) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 32: Table 5. Ups Cabinet Clearances

    From Back of Cabinet with Rear Exhaust From Back of Cabinet with Top Exhaust None Required From Right Side of Cabinet None Required None Required From Left Side of Cabinet Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 33 [74] Torque M10 Bolt: 42 Nm (31 lb-ft.) 47.4 [1.9] 58 [2.3] 388 [15.3] [22] 630 [24.8] 960 [37.8] Front Right Side Dimensions are in millimeters [Inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 34 UPS Installation Plan and Unpacking Figure 5. UPS Cabinet Dimensions (Top and Bottom Views) Top View Top View (Top Exhaust Option) (Rear Exhaust Option) Front Front Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 35 Figure 6. UPS (100/150 kW UPS) with Left or Right-Mounted Sidecar Dimensions (Front Views) 1880 [ 74.0 ] [ 30.0 ] [ 30.0 ] Front Front UPS With Left-Mounted Sidecar UPS With Right-Mounted Sidecar Dimensions are in millimeterse [Inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 36 [ 30 ] [ 30 ] Front Front 1067 Bottom Bottom [ 42 ] UPS With Left-Mounted Sidecar UPS With Right-Mounted Sidecar Dimensions are in millimeters [Inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 37 Figure 8. UPS (150 kW UPS) with Left or Right-Mounted Bypass-Sidecar Dimensions (Front Views) 1880 [74.0] 560 [22.0] 560 [22.0] 875 [34.45] 875 [34.45] Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 38 DC Landing Plate Bottom View UPS with Left-Mounted Bypass Sidecar UPS with Right-Mounted Bypass Sidecar (Top Exhaust Option Shown) (Top Exhaust Option Shown) Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 39 NOTE 1: All examples are shown with top exhaust option. NOTE 2: The UPS Front Floor Mounting Bracket’s mounting dimensions are identical to the Rear Floor Mounting Bracket dimensions. Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 40 Torque 87 Nm 1/2” Grade 5 Torque 64 lb-ft UPS (100/150 kW UPS) with Right-Mounted Sidecar UPS (150 kW UPS) with Large Right-Mounted Sidecar Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 41: Table 6. Three-Wire Ups - Center Of Gravity Dimensions

    Eaton 93PM Gen 2 4W 150 with 2 UPM Installed 969 [38.1] 539 [21.2] 277 [10.9] 433 (954) Eaton 93PM Gen 2 4W 150 with 3 UPM Installed Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 42: Table 8. Three-Wire Ups (100/150 Kw Ups) With Sidecar - Center Of Gravity Dimensions

    Eaton 93PM Gen 2 4W 100/150-2 with 4–Breaker Sidecar 908 [35.7] 564 [22.2] 365 [14.4] 519 (1144) Eaton 93PM Gen 2 4W 100/150-3 with 4–Breaker Sidecar 941 [37.1] 565 [22.2] 358 [14.1] 562 (1239) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 43: Table 10. Three-Wire Ups (150 Kw Ups) With Sidecar - Center Of Gravity Dimensions

    552 (1217) Eaton 93PM Gen 2 3W 150–2 with 4-Breaker Sidecar 955 [37.6] 554 [21.8] 391 [15.4] 595 (1312) Eaton 93PM Gen 2 3W 150–3 with 4-Breaker Sidecar Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 44: Table 11. Four-Wire Ups (150 Kw Ups) With Sidecar - Center Of Gravity Dimensions

    [3.50] EMERGENCY POWER OFF UPS SYSTEM 114.3 95.3 [4.50] [3.57] 1.57 [0.40] Needed to remove key 1/2” Knockout Pattern (Typical 5 sides) Dimensions are in millimeters (inches) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 45 Refer to national and local electrical codes for acceptable external wiring practices. • To allow for future power upgrades, Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size instead of the derated kW ordered.
  • Page 46 If the maintenance bypass solution being installed does not provide such functionality, DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass. • The Eaton 93PM Gen 2 UPS provides backfeed detection and protection through a shunt trip mechanism of the bypass input breaker. IMPORTANT If an Eaton 93PM Gen 2 UPS is ordered with: •...
  • Page 47 Trip. For external wiring recommendations, including the minimum AWG size of external wiring, see Table 12 through Table 17. Wire sizes listed are for copper wiring only. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 48 AC Output to Critical Load (Three-Wire UPS) Amps Full Load Current (3) Phases, (1) Ground Minimum Conductor Size (Phase A, B, and C) AWG or kcmil Number per Phase (each) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 49: Table 12. Three-Wire Ups - Input/Output Ratings And Wiring Recommendations: 20-50 Kw (480/480)

    Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. Table 13. Three-Wire UPS - Input/Output Ratings and Wiring Recommendations: 60–100 kW (480/480)
  • Page 50: Table 13. Three-Wire Ups - Input/Output Ratings And Wiring Recommendations: 60-100 Kw (480/480)

    Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. Table 14. Three-Wire UPS - Input/Output Ratings and Wiring Recommendations: 110–150 kW (480/480)
  • Page 51: Table 14. Three-Wire Ups - Input/Output Ratings And Wiring Recommendations: 110-150 Kw (480/480)

    Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. Table 15. Four-Wire UPS - Input/Output Ratings and Wiring Recommendations: 20–50 kW (480/480)
  • Page 52: Table 15. Four-Wire Ups - Input/Output Ratings And Wiring Recommendations: 20-50 Kw (480/480)

    Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 53: Table 16. Four-Wire Ups - Input/Output Ratings And Wiring Recommendations: 60-100 Kw (480/480)

    Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 54: Table 17. Four-Wire Ups - Input/Output Ratings And Wiring Recommendations: 110-150 Kw (480/480)

    Full Load Current, (3) Phases, (1) Neutral – see Amps Note, (1) Ground Neutral Current Minimum Conductor Size (Phase A, B, and C) Number per Phase AWG or kcmil (each) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 55: Table 18. Ups External Power Cable Terminations

    Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in...
  • Page 56: Table 19. Supplied External Wiring Terminal Hardware Kit

    Critical Load Conical Washer Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 57: Table 20. Recommended Installation Parts And Tools (Not Supplied By Eaton)

    500 MCM Manual Hydraulic Crimp Tool 14 Ton Die Set NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help). Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See...
  • Page 58: Table 21. Three-Wire Ups - Power Cable Conduit Recommendations

    50 kW 93PM Gen 2 150-2 AC Output (N+1) (A, B, C, Ground) Battery - 216 Cells (432V) Battery - 240 Cells (480V) 1–1/4 (Positive, Negative, Ground) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 59 90 kW 93PM Gen 2 150-3 AC Output 1-1/2 (N+1) (A, B, C, Ground) Battery - 216 Cells (432V) Battery - 240 Cells (480V) (Positive, Negative, Ground) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 60 (A, B, C, Ground 130 kW 93PM Gen 2 150-3 AC Output (A, B, C, Ground) Battery - 216 Cells (432V) Battery - 240 Cells (480V) 1-1/2 (Positive, Negative, Ground) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 61 AC Output (A, B, C, Ground) Battery - 216 Cells (432V) Battery - 240 Cells (480V) 1-1/2 (Positive, Negative, Ground) NOTE Wires per conduit include ground wire. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 62: Table 22. Four-Wire Ups - Power Cable Conduit Recommendations

    (A, B, C, Neutral, Ground) 50 kW 93PM Gen 2 150-2 AC Output (N+1) 1-1/4 (A, B, C, Neutral, Ground) Battery - 240 Cells (480V) 1–1/4 (Positive, Negative, Ground) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 63 (A, B, C, Neutral, Ground) 90 kW 93PM Gen 2 150-3 AC Output (N+1) (A, B, C, Neutral, Ground) Battery - 240 Cells (480V) (Positive, Negative, Ground) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 64 (A, B, C, Neutral, Ground) 130 kW 93PM Gen 2 150-3 AC Output 2-1/2 (A, B, C, Neutral, Ground) Battery - 240 Cells (480V) 1-1/2 (Positive, Negative, Ground) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 65 If an output lockable disconnect is required, it is to be supplied by the customer. The following table lists the recommended rating for input and bypass circuit breakers. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 66: Table 23. Recommended Input And Bypass Circuit Breaker Ratings

    To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table 23 in accordance with the NEC, ANSI/NFPA 70. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 67: Table 24. Recommended Output Circuit Breaker Ratings

    80 kW 93PM Gen 2 150-3 (N+1) 100% Rated 100A 80% Rated 150A 93PM Gen 2 150-2 90 kW 93PM Gen 2 150-3 (N+1) 100% Rated 110A Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 68: Table 25. Recommended Dc Input Battery Disconnect Circuit Breaker Ratings

    93PM Gen 2 150-2 (N+1) 93PM Gen 2 150-2 60 kW 150A 150A 93PM Gen 2 150-3 (N+1) 93PM Gen 2 150-2 70 kW 175A 200A 93PM Gen 2 150-3 (N+1) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 69 When installing external interface wiring between a building alarm, relay output, battery breaker trip, or Minislot and the UPS interface terminals, conduit must be installed between each device and the UPS cabinet. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 70 Warranty for details. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (a minimum two-week notice is required) to reserve a preferred startup date. The UPS cabinet is heavy (see Table 3).
  • Page 71 UPS Installation Plan and Unpacking Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. ATTENTION! Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement.
  • Page 72 UPS Installation Plan and Unpacking Figure 16. UPS Cabinet as Shipped on Pallet Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 73 UPS Installation Plan and Unpacking Figure 17. UPS Cabinet with Left or Right-Mounted Sidecar as Shipped on Pallet UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 74: Ups System Installation

    (see Figure Figure 13, or Figure 14 and their corresponding Center of Gravity tables for the UPS cabinet center of gravity measurements). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 75 If a sidecar is attached to the UPS, loosen, but do not remove, the sidecar skid mounting bolts holding the sidecar pallet skids to the sidecar front and rear supports, and to the left and right supports (see Figure 19 for deatils. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 76 If a sidecar is attached to the UPS, remove the hardware loosened in Step 5. Pull the pallet skids out from under the metal angle supports without disturbing the jacking bolts. Recycle the pallet skids and hardware in a responsible manner. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 77 21. If permanently mounting the UPS using the optional front and rear floor mounting bracket kit, proceed to Step 22; otherwise, proceed to Step 26. 22. Proceed to Step 26. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 78 1.8 For More Information, for installation instructions. IMPORTANT If the Eaton 93PM Gen 2 UPS has a SIAC-B, the Integrated Battery Cabinet must be installed on the opposite side of the UPS away from the SIAC-B. IMPORTANT Si l'onduleur Eaton 93PM Gen 2 est équipé d'un SIAC-B, l'armoire de batteries intégrée doit être installée du côté...
  • Page 79 If Four–Wire installation, connect the AC Output Neutral to the E12 Neutral terminals. See Figure 25 Four–Wire power terminal details. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 80 AC Input and Output, and DC Input Front Bottom View Top Entry Conduit Landings for Customer Interface Wiring NOTE: Remove panels to drill or punch conduit holes. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 81 AC Input/Output DC Input Conduit Plates: Interface Wiring Front Conduit Plate: DC Input Conduit Plate: AC Input/Output Bottom View NOTE: Remove panels to drill or punch conduit holes. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 82 Inter-cabinet wiring access to route interface wiring between cabinets. Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Left Side View Right Side View Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 83 UPS System Installation Figure 23. Power Terminal Locations DC Input from Battery AC Input to UPS Rectifier AC Output to Critical Load AC Input to UPS Bypass Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 84 Phase B (E7) UPS Bypass DC Input from Battery - (E5) Phase A (E6) DC Input from Battery + (E4) Cabinet Equipment Cabinet Bonding Post Ground Terminals Bonding Post Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 85 DC Input from Battery - (E5) AC Input to UPS Bypass Phase B (E7) DC Input from Battery + (E4) Phase A (E6) Cabinet Equipment Cabinet Bonding Post Ground Terminals Bonding Post Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 86 If Four–Wire installation, connect the AC Output Neutral to the E12 Neutral terminals. See Figure 28 Figure 29 for Four–Wire power terminal details. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 87 PHASE B (E10) PHASE C (E11) E6, E7 , E8 AC INPUT TO BYPASS GROUND COMPRESSION ( 2X ) GROUND STUDS LUGS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 88 PHASE B (E10) PHASE C (E11) GROUND E6, E7 , E8 COMPRESSION AC INPUT LUGS TO BYPASS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 89 PHASE B (E10) PHASE C (E11) E6, E7 , E8, E12 AC INPUT TO BYPASS ( 2X ) GROUND STUDS FOR CABINET TO GROUND COMPRESSION CABINET WIRING LUGS Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 90 PHASE B (E10) PHASE C (E11) E6, E7 , E8, E12 GROUND AC INPUT COMPRESSION TO BYPASS LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 91 If Four–Wire installation, connect the AC Output Neutral to the E12 Neutral terminals. See Figure 32 Figure 33 for Four–Wire power terminal details Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 92 BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION ( 2X ) GROUND STUDS LUGS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 93 BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 94 BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION ( 2X ) GROUND STUDS LUGS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 95 E5 ( - ) AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 96 If Four–Wire installation, connect the AC Output Neutral to the E12 Neutral terminals. See Figure 36 Figure 37 for Four–Wire power terminal details. 10. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 97 BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION ( 2X ) GROUND STUDS LUGS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 98 BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 99 BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) ( 2X ) GROUND STUDS GROUND COMPRESSION FOR CABINET TO LUGS CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 100 E5 ( - ) AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 101 UPS System Installation Figure 38. RIB Terminal Detail AC Input to Rectifier Input Breaker PHASE A (RIB-1) PHASE B (RIB-3) PHASE C (RIB-5) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 102 Route and connect the battery cables between the UPS and battery cabinet or battery disconnect according to the instructions in the Eaton Samsung Gen 3 Battery Cabinet Installation and Operation Manual, Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton...
  • Page 103: Table 26. List Of Interface And Control Wiring Connection Topics

    UPS interface terminal locations. Proceed to Step 13. Bottom Entry Wiring. Remove the bottom interface entry conduit landing plates to drill or punch holes (see Figure 41). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 104 16. Close the UPS outside door and secure the latch. Figure 39. Interface Terminal Locations Upper Cabinet View of UPS Minislot Communication Bays Interface Terminals Pull Chain and CAN Terminals Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 105: Figure 40. Interface Terminal Detail

    Cabinet Stiffener Bar Minislot Communication Bay 1 Minislot Communication Bay 4 Relay Output Terminals Pull Chain and Host USB CAN Terminals Device USB REPO Terminals Building Alarm Terminals RS-232 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 106: Figure 41. Bottom Access Interface Wiring Location

    UPS System Installation Figure 41. Bottom Access Interface Wiring Location Wire Tie Anchors Bottom Access Interface Wiring Channel Bottom Entry Conduit Landings for Customer Interface Wiring Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 107: Figure 42. Wire Tie Anchors

    #14 #30 AWG Wires #18 AWG (0.22-0.25 Nm) Building Alarm 3 Return dry contact closure Building Alarm 4 Building Alarm 4 Return Building Alarm 5 Building Alarm 5 Return Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 108: Figure 43. Building Alarm Terminal Block Connector Assignments

    (0.22-0.25 Nm) Relay Contact NO Output: General purpose normally-open (NO) relay Relay Contact contact Common Figure 44. Relay Contact Terminal Block Connector Assignments UPS Relay Output NC_Out NO_Out Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 109: Table 29. Sidecar Mis And Rib Breaker Monitoring Connection And Wire Terminations

    MIS - Aux COM MIS - Aux NC 2 lb in Twisted Pair Wires #14 #30 AWG #18 AWG (0.22-0.25 Nm) RIB - Aux COM RIB - Aux NC Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 110: Figure 45. Sidecar Tb1 And Tb2 Terminal Locations

    Aux COM - MBP 2 Aux NC - MBP 3 2 / 3 / 4 Breaker SIAC-B Aux COM - MIS 9 Aux NC - MIS 10 Front of UPS Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 111 15. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 16. If removed, reinstall the sidecar front panel and secure with the retained hardware. 17. Close the UPS outside door and secure the latch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 112: Figure 46. Shunt Trip And Auxiliary Terminal Block (Cn8) Location

    UPS System Installation Figure 46. Shunt Trip and Auxiliary Terminal Block (CN8) Location Shunt Trip and Auxillary Terminals for Battery and Bypass (CN8 Terminal Block) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 113 Table 26 for next option to install; otherwise, proceed to Step 17. 17. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 114: Figure 47. Bypass Shunt Trip, Battery Shunt Trip And Detect Terminal Detail

    48 Vdc Battery Shunt Trip + 48 Vdc Battery Aux Input: Contacts used to monitor 1–A auxiliary contacts on battery 48 Vdc Battery Aux breaker or disconnect 1–B Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 115 10. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 11. If removed, reinstall the sidecar front panel and secure with the retained hardware. 12. Close the UPS outside door and secure the latch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 116 15. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 16. If removed, reinstall the sidecar front panel and secure with the retained hardware. 17. Close the UPS outside door and secure the latch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 117 Remove the cabinet stiffener bar (see Interface Terminal Locations) before installing or removing Minislot cards. Reinstall the bar after the procedure is completed. For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.9 Getting Help). To install wiring: If not already installed, install the LAN drop.
  • Page 118 Bottom Entry Wiring. Remove the bottom interface entry conduit landing plate to drill or punch holes (see Figure 41). 10. Reinstall the interface entry plate and install the conduit. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 119: Figure 48. Repo Switch

    14. Connect the REPO wiring as shown in Table 31 Figure 50 for a normally-open REPO or Table 32 Figure 51 for a normally-closed REPO for a normally-closed REPO. See paragraph 3.2.3 UPS System Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 120: Figure 49. Repo Terminal Block Connector Assignments

    2 lb in Input: Normally-open dry (0.22-0.25 Nm) Twisted Pair Wires contact used to activate UPS #18 AWG #30 AWG 4 NO EPO_ EPO from a remote switch Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 121: Figure 50. Normally-Open Repo Switch Wiring

    2 lb in Input: Normally-closed (0.22-0.25 Nm) dry contact used to Twisted Pair Wires #18 #16 #30 AWG activate UPS EPO from 4 NO GND- a remote switch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 122: Figure 51. Normally-Closed Repo Switch Wiring

    Make a copy of the Installation Checklist before filling it out, and retain the original. After the installation is complete, an Eaton Customer Service Engineer must verify the operation of the UPS system and commission it to support the critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters.
  • Page 123 Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) o Air conditioning equipment is installed and operating correctly. o The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) o Adequate workspace exists around the UPS and other cabinets.
  • Page 124 UPS System Installation Notes _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 125: Figure 52. Main Elements Of The Ups System

    U U P P S S S S y y s s t t e e m m O O v v e e r r v v i i e e w w The Eaton 93PM Gen 2 UPS is a continuous-duty, solid-state, transformerless, three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
  • Page 126: Understanding Ups Operation

    5 5 . . 2 2 . . 1 1 M M o o d d e e s s The Eaton 93PM Gen 2 UPS supports a critical load in four different modes of operation: •...
  • Page 127: Figure 53. Path Of Current Through The Ups In Energy Saver System Mode

    Bypass Input Switch Switch Rectifier Input Output Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 128: Figure 54. Path Of Current Through The Ups In Normal Mode

    Bypass Input Switch Rectifier Input Output Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 129: Figure 55. Path Of Current Through The Ups In Bypass Mode

    Bypass Input Switch Rectifier Input Output Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 130: Figure 56. Path Of Current Through The Ups In Battery Mode

    Bypass Input Switch Rectifier Input Output Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 131: Figure 57. Eaton 93Pm Gen 2 Three-Wire Ups System Oneline

    3. DASHED LINES OUTSIDE OF UPS INDICATE OPTIONAL EQUIPMENT CABINETS. BREAKER 4. BACKFEED PROTECTION IS NOT PROVIDED AS A PART OF UPS. CUSTOMER SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 132: Figure 58. Eaton 93Pm Gen 2 Three-Wire Ups With Top Entry Sidecar System Oneline

    UPS Oneline Schematics Figure 58. Eaton 93PM Gen 2 Three-Wire UPS with Top Entry Sidecar System Oneline Parallel CAN Pull Chain AC INPUT TO AC INPUT TO RECTIFIER BYPASS Mini-Slot (SOURCE 1) (SOURCE 2) Remote EPO Interface Interface Board E1,E2,E3...
  • Page 133: Figure 59. Eaton 93Pm Gen 2 Three-Wire Ups With Bypass Sidecar (Siac-B) System Oneline

    UPS Oneline Schematics Figure 59. Eaton 93PM Gen 2 Three-Wire UPS with Bypass Sidecar (SIAC-B) System Oneline Parallel CAN Pull Chain AC INPUT TO AC INPUT TO RECTIFIER BYPASS Mini-Slot (SOURCE 1) (SOURCE 2) Remote EPO Interface Interface Board E1,E2,E3...
  • Page 134: Figure 60. Ups Control Panel And Door Latch Location

    U U s s i i n n g g t t h h e e C C o o n n t t r r o o l l P P a a n n e e l l The following paragraphs describe the UPS control panel, including controls and indicators, and how to monitor UPS operation. The control panel is shown in Figure Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 135: Figure 61. Ups Control Panel

    The four symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED) lamps work with the alarm horn to provide the operating status of the UPS. Table 33 describes the status indicators. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 136: Table 33. Status Indicators

    All functions and commands are accessed by touching or tapping the screen tabs or buttons. When text input is required, either a Qwerty keyboard or numeric keypad will be displayed. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 137: Figure 62. Parts Of The Lcd

    The UPS navigation tab menu bar allows you to display data in the information area to help you monitor and control UPS operation. Table 34 shows the basic menu structure. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 138: Figure 63. Main Menu And Mimic Screen

    The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation of the operating status of the system. Figure 63. Main Menu and Mimic Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 139: Table 35. Display Menu Operation

    The end of the log (the most recent events) is displayed first; scroll upward to view older event listings. To scroll through the events, press the up or down scroll bar. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 140: Figure 64. Typical Meters Summary Screen

    Statistics Details Tap the desired statistic button to display the detailed statistic screen. Controls See paragraph 7.2.8 System Controls for details. Figure 64. Typical Meters Summary Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 141: Figure 65. Typical Active Events Screen

    UPS Operating Instructions Figure 65. Typical Active Events Screen Figure 66. Typical System Log Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 142: Figure 67. Typical Settings User Screen

    UPS Operating Instructions Figure 67. Typical Settings User Screen Figure 68. Typical Information Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 143: Figure 69. Typical About Screen

    UPS Operating Instructions Figure 69. Typical About Screen Figure 70. Typical Settings Configuration 1 Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 144: Figure 71. Typical Settings Configuration 2 Screen

    7 7 . . 2 2 . . 7 7 S S i i g g n n I I n n The Controls and Setting screens are restricted. The user must sign in using a password to gain access. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 145: Figure 73. Sign In Password Screen

    Level 1 default password is 111111. Settings Level 2 default password is 101010. Sign in is complete. Tap continue to return to previous screen. Figure 73. Sign In Password Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 146: Figure 74. Sign In Keypad

    Bypass mode from Double Conversion mode. Charger TURN ON CHARGER/TURN OFF CHARGER sets the battery charger on or off. Battery Test RUN BATTERY TEST starts the battery test. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 147: Figure 75. Typical System Control Screen

    UPS Operating Instructions Table 37. Typical System Status Messages Message Function Double Conversion; Bypass; ESS Bypass Off; On; Available Charger Charger Resting; Charger Figure 75. Typical System Control Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 148: Figure 76. Typical Ups Control Screen

    UPS Operating Instructions Figure 76. Typical UPS Control Screen Figure 77. Typical UPM Select Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 149: Figure 78. Typical Upm Control Screen

    UPS Operating Instructions Figure 78. Typical UPM Control Screen Figure 79. Typical EAA Control Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 150 Verify no alarms are active. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed. Tap the GO TO BYPASS button. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 151: Figure 80. Dc Start Button Location

    Press the DC Start button on the front of each UPM to power on the UPM power supply. (See Figure 80 for DC Start Button location). Figure 80. DC Start Button Location DC Start Button 10. Close the door and secure the latch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 152 Tap the MODULES CONTROLS tab on the secondary Control menu navigation bar. The UPM Select screen is displayed. On the UPM Select screen, select the UPM to start. The UPM Control Screen is displayed. Tap the START MODULE button. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 153 Tap the EAA CONTROLS tab on the secondary Control menu navigation bar. The EAA CONTROLS screen is displayed. Tap the DISABLE ESS button. The UPS transfers to Double Conversion mode. The NORMAL status indicator is illuminated. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 154 7 7 . . 3 3 . . 1 1 2 2 S S i i n n g g l l e e U U P P M M R R e e s s t t a a r r t t To restart a single UPM from a shutdown state: Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 155 Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Tap the TURN OFF CHARGER button. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 156 To restart the UPS after using the LOAD OFF follow the procedure in paragraph 7.3.1 Starting the UPS in Double Conversion Mode 7.3.2 Starting the UPS in Bypass Mode. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 157 To use the REPO switch: Firmly push the red pushbutton until it locks into place. The switch latches into the activated state (see Figure 81). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 158 Attendez au moins 5 minutes avant d'accéder aux composants internes. Figure 81. REPO Operation Activated Deactivated (Pushbutton locked into place.) (Unlock pushbutton to release.) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 159: Table 38. Irc-Ms Default Triggers

    M M i i n n i i s s l l o o t t C C a a r r d d s s The Eaton 93PM Gen 2 UPS has four standard, factory-installed Minislot communication bays. The UPS is...
  • Page 160 It’s also powered by CA Technologies, bringing together the best in hardware and software. PredictPulse Service is included at no charge during the first year of Eaton 93PM Gen 2 UPS operation (warranty period) along with the required connectivity parts. Beyond that, it may be purchased with Eaton Support Agreements or as a standalone subscription after the initial warranty expires.
  • Page 161 Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
  • Page 162: Ups Maintenance

    Each battery string is an energy source in itself. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. Observe these precautions when working on or around batteries: •...
  • Page 163 Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated or the Normal status indicator is not illuminated, contact an Eaton service representative. 9 9 . . 2 2 . . 2 2 M M O O N N T T H H L L Y Y M M a a i i n n t t e e n n a a n n c c e e...
  • Page 164 à fonctionner sans filtres installés. Close the front door and secure the latch. Record maintenance results and any corrective actions in a suitable log. Figure 83. Air Filter Location Air Filter Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 165 9 9 . . 2 2 . . 4 4 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
  • Page 166 M M a a i i n n t t e e n n a a n n c c e e T T r r a a i i n n i i n n g g A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance.
  • Page 167 Eaton 93PM Gen 2 150-3 (N+1) Eaton 93PM Gen 2 150-2 90 kW Eaton 93PM Gen 2 150-3 (N+1) Eaton 93PM Gen 2 150-2 100 kW Eaton 93PM Gen 2 150-3 (N+1) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 168: Product Specifications

    Output Voltage Phase Displacement < 2.5° for 100% maximum load imbalance (linear load) Frequency Regulation 0.1 Hz free running Synchronous to Bypass ± 4 Hz (default setting) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 169 Meets IEC 61000-4-2 Level 3 specifications and CISPR 24. Withstands up to 4 kV (ESD) contact pulse without damage and with no disturbance or adverse effect to the critical load. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
  • Page 170 C C h h a a p p t t e e r r 1 1 1 1 W W a a r r r r a a n n t t y y To view the UPS warranty please click on the link or copy the address to download from the Eaton website: UPS Product Warranty https://www.eaton.com/content/dam/eaton/products/backup-power-ups-surge-it-power-distribution/backup-...
  • Page 171 P-16400103001 P-164001030 01...