Dear Customer, On behalf of everyone at Eaton, we thank you for partnering with us, for trusting us to maintain your business continuity and for preventing downtime at your facility. Our suite of backup power, power distribution and power management products are designed to protect you from a host...
Page 5
4 4 U U P P S S S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n ....................................................6 6 2 2 4.1 Preliminary Installation Information....................... 62 4.2 Unloading the UPS Cabinet from the Pallet..................... 62 4.3 Integrated Battery Cabinet Installation......................66 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 6
7.2.6 Display Menu Operation........................127 7.2.7 Sign In............................132 7.2.8 System Controls..........................134 7.3 Single UPS Operation ..........................138 7.3.1 Starting the UPS in Double Conversion Mode ..................138 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 7
1 1 0 0 P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s ................................................... . 1 1 5 5 5 5 10.1 Models ............................... 155 10.2 Specifications............................156 10.2.1 UPS Input............................156 10.2.2 UPS Output ........................... 156 10.2.3 UPS Environmental ......................... 157 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 8
1 1 1 1 W W a a r r r r a a n n t t y y ........................................................... . 1 1 5 5 8 8 viii Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 9
Four-Wire 100/150 kW UPS with SIAC-B (4-Breaker) Power Terminal Locations ........87 Figure 37. Four-Wire 150 kW UPS with SIAC-B (4-Breaker) Power Terminal Locations ..........88 Figure 38. RIB Terminal Detail........................89 Figure 39. Interface Terminal Locations......................92 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Eaton 93PM Gen 2 Three-Wire UPS System Oneline ................. 119 Figure 58. Eaton 93PM Gen 2 Three-Wire UPS with Top Entry Sidecar System Oneline .......... 120 Figure 59. Eaton 93PM Gen 2 Three-Wire UPS with Bypass Sidecar (SIAC-B) System Oneline........121 Figure 60.
Page 11
List of Figures Figure 81. REPO Operation ........................146 Figure 82. Optional Minislot Cards ....................... 147 Figure 83. Air Filter Location ........................152 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 12
Table 35. Display Menu Operation ....................... 127 Table 36. Controls Menu Operation ......................134 Table 37. Typical System Status Messages....................135 Table 38. IRC-MS Default Triggers ....................... 147 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 13
AC power to protect the customer's load from power failures. The Eaton 93PM Gen 2 UPS online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
Page 14
Introduction Figure 1. Eaton 93PM Gen 2 UPS Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 15
Introduction Figure 2. Eaton 93PM Gen 2 100/150 kW UPS with Sidecar UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 16
Alarm Contact – One alarm contact is provided for connection to equipment at the facility, such as a light, an audible alarm, or a computer terminal. The equipment connected to this contact alerts you to a UPS alarm. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 17
1 1 . . 1 1 . . 5 5 I I n n t t e e r r n n a a l l R R e e d d u u n n d d a a n n c c y y To deliver greater reliability, the Eaton 93PM Gen 2 UPS can be configured for internal redundancy. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM.
Page 18
The cabinets match the UPS cabinet in style and color. The IAC-D may be installed on either the right or left side of the UPS cabinet. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 19
1 1 . . 2 2 . . 7 7 A A d d d d i i t t i i o o n n a a l l O O u u t t p p u u t t S S u u r r g g e e P P r r o o t t e e c c t t i i o o n n The Eaton 93PM Gen 2 UPS complies with ANSI 62.41 for line surges. However, if added security is required an additional Surge Protection Device (SPD) can be installed.
Page 20
U U s s i i n n g g T T h h i i s s M M a a n n u u a a l l This manual describes how to install and operate the Eaton 93PM Gen 2 UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation.
Wire IAC-PD, 480V 4–Wire IAC-PD) Installation and Operation Manual for the following additional Phillips and Pozidriv are registered trademarks of Phillips Screw Company. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be information: Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates.
Page 22
1 1 . . 1 1 0 0 E E q q u u i i p p m m e e n n t t R R e e g g i i s s t t r r a a t t i i o o n n Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number: Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 23
ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors. Attempting to alter wiring can cause injury. • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
à la terre si des charges y sont raccordées. • Ne pas ouvrir ni abîmer les batteries. L’électrolyte qu’elles contiennent est dangereux pour la peau et les yeux. Il peut être toxique. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 25
• Keep surroundings uncluttered, clean, and free from excess moisture. • Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 26
Maintenir les lieux rangés, propres et exempts d’une humidité excessive. • Respecter les étiquettes DANGER, MISE EN GARDE et AVERTISSEMENT se trouvant à l’intérieur et à l’extérieur de l’équipement. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Warranty for details. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (a minimum two-week notice is required) to reserve a preferred startup date. 3 3 . . 1 1 C C r r e e a a t t i i n n g g a a n n I I n n s s t t a a l l l l a a t t i i o o n n P P l l a a n n Before installing the UPS system, read and understand how this manual applies to the system being installed.
Page 28
If the environment created by this microclimate exceeds the UPS operating specification, the UPS reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns for any servers that are exposed to them. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Des températures de fonctionnement supérieures à la plage recommandée entraîneront une diminution de la durée de vie et des performances de la batterie et pourront réduire ou annuler la garantie de la batterie. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
The UPS equipment operating environment must meet the weight requirements shown in Table 3 and the size requirements shown in Figure 4 through Figure 11. Dimensions are in millimeters (inches). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
From Back of Cabinet with Rear Exhaust From Back of Cabinet with Top Exhaust None Required From Right Side of Cabinet None Required None Required From Left Side of Cabinet Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 33
[74] Torque M10 Bolt: 42 Nm (31 lb-ft.) 47.4 [1.9] 58 [2.3] 388 [15.3] [22] 630 [24.8] 960 [37.8] Front Right Side Dimensions are in millimeters [Inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 34
UPS Installation Plan and Unpacking Figure 5. UPS Cabinet Dimensions (Top and Bottom Views) Top View Top View (Top Exhaust Option) (Rear Exhaust Option) Front Front Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 35
Figure 6. UPS (100/150 kW UPS) with Left or Right-Mounted Sidecar Dimensions (Front Views) 1880 [ 74.0 ] [ 30.0 ] [ 30.0 ] Front Front UPS With Left-Mounted Sidecar UPS With Right-Mounted Sidecar Dimensions are in millimeterse [Inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 36
[ 30 ] [ 30 ] Front Front 1067 Bottom Bottom [ 42 ] UPS With Left-Mounted Sidecar UPS With Right-Mounted Sidecar Dimensions are in millimeters [Inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 37
Figure 8. UPS (150 kW UPS) with Left or Right-Mounted Bypass-Sidecar Dimensions (Front Views) 1880 [74.0] 560 [22.0] 560 [22.0] 875 [34.45] 875 [34.45] Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 38
DC Landing Plate Bottom View UPS with Left-Mounted Bypass Sidecar UPS with Right-Mounted Bypass Sidecar (Top Exhaust Option Shown) (Top Exhaust Option Shown) Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 39
NOTE 1: All examples are shown with top exhaust option. NOTE 2: The UPS Front Floor Mounting Bracket’s mounting dimensions are identical to the Rear Floor Mounting Bracket dimensions. Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 40
Torque 87 Nm 1/2” Grade 5 Torque 64 lb-ft UPS (100/150 kW UPS) with Right-Mounted Sidecar UPS (150 kW UPS) with Large Right-Mounted Sidecar Dimensions are in millimeters [inches] Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
[3.50] EMERGENCY POWER OFF UPS SYSTEM 114.3 95.3 [4.50] [3.57] 1.57 [0.40] Needed to remove key 1/2” Knockout Pattern (Typical 5 sides) Dimensions are in millimeters (inches) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 45
Refer to national and local electrical codes for acceptable external wiring practices. • To allow for future power upgrades, Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size instead of the derated kW ordered.
Page 46
If the maintenance bypass solution being installed does not provide such functionality, DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass. • The Eaton 93PM Gen 2 UPS provides backfeed detection and protection through a shunt trip mechanism of the bypass input breaker. IMPORTANT If an Eaton 93PM Gen 2 UPS is ordered with: •...
Page 47
Trip. For external wiring recommendations, including the minimum AWG size of external wiring, see Table 12 through Table 17. Wire sizes listed are for copper wiring only. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 48
AC Output to Critical Load (Three-Wire UPS) Amps Full Load Current (3) Phases, (1) Ground Minimum Conductor Size (Phase A, B, and C) AWG or kcmil Number per Phase (each) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Full Load Current, (3) Phases, (1) Neutral – see Amps Note, (1) Ground Neutral Current Minimum Conductor Size (Phase A, B, and C) Number per Phase AWG or kcmil (each) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Chapter 6 UPS Oneline Schematics. Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed. The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in...
Critical Load Conical Washer Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
500 MCM Manual Hydraulic Crimp Tool 14 Ton Die Set NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help). Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See...
Page 65
If an output lockable disconnect is required, it is to be supplied by the customer. The following table lists the recommended rating for input and bypass circuit breakers. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table 23 in accordance with the NEC, ANSI/NFPA 70. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
93PM Gen 2 150-2 (N+1) 93PM Gen 2 150-2 60 kW 150A 150A 93PM Gen 2 150-3 (N+1) 93PM Gen 2 150-2 70 kW 175A 200A 93PM Gen 2 150-3 (N+1) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 69
When installing external interface wiring between a building alarm, relay output, battery breaker trip, or Minislot and the UPS interface terminals, conduit must be installed between each device and the UPS cabinet. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 70
Warranty for details. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (a minimum two-week notice is required) to reserve a preferred startup date. The UPS cabinet is heavy (see Table 3).
Page 71
UPS Installation Plan and Unpacking Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. ATTENTION! Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement.
Page 72
UPS Installation Plan and Unpacking Figure 16. UPS Cabinet as Shipped on Pallet Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 73
UPS Installation Plan and Unpacking Figure 17. UPS Cabinet with Left or Right-Mounted Sidecar as Shipped on Pallet UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
(see Figure Figure 13, or Figure 14 and their corresponding Center of Gravity tables for the UPS cabinet center of gravity measurements). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 75
If a sidecar is attached to the UPS, loosen, but do not remove, the sidecar skid mounting bolts holding the sidecar pallet skids to the sidecar front and rear supports, and to the left and right supports (see Figure 19 for deatils. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 76
If a sidecar is attached to the UPS, remove the hardware loosened in Step 5. Pull the pallet skids out from under the metal angle supports without disturbing the jacking bolts. Recycle the pallet skids and hardware in a responsible manner. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 77
21. If permanently mounting the UPS using the optional front and rear floor mounting bracket kit, proceed to Step 22; otherwise, proceed to Step 26. 22. Proceed to Step 26. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 78
1.8 For More Information, for installation instructions. IMPORTANT If the Eaton 93PM Gen 2 UPS has a SIAC-B, the Integrated Battery Cabinet must be installed on the opposite side of the UPS away from the SIAC-B. IMPORTANT Si l'onduleur Eaton 93PM Gen 2 est équipé d'un SIAC-B, l'armoire de batteries intégrée doit être installée du côté...
Page 79
If Four–Wire installation, connect the AC Output Neutral to the E12 Neutral terminals. See Figure 25 Four–Wire power terminal details. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 80
AC Input and Output, and DC Input Front Bottom View Top Entry Conduit Landings for Customer Interface Wiring NOTE: Remove panels to drill or punch conduit holes. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 81
AC Input/Output DC Input Conduit Plates: Interface Wiring Front Conduit Plate: DC Input Conduit Plate: AC Input/Output Bottom View NOTE: Remove panels to drill or punch conduit holes. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 82
Inter-cabinet wiring access to route interface wiring between cabinets. Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Left Side View Right Side View Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 83
UPS System Installation Figure 23. Power Terminal Locations DC Input from Battery AC Input to UPS Rectifier AC Output to Critical Load AC Input to UPS Bypass Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 84
Phase B (E7) UPS Bypass DC Input from Battery - (E5) Phase A (E6) DC Input from Battery + (E4) Cabinet Equipment Cabinet Bonding Post Ground Terminals Bonding Post Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 85
DC Input from Battery - (E5) AC Input to UPS Bypass Phase B (E7) DC Input from Battery + (E4) Phase A (E6) Cabinet Equipment Cabinet Bonding Post Ground Terminals Bonding Post Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 86
If Four–Wire installation, connect the AC Output Neutral to the E12 Neutral terminals. See Figure 28 Figure 29 for Four–Wire power terminal details. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 87
PHASE B (E10) PHASE C (E11) E6, E7 , E8 AC INPUT TO BYPASS GROUND COMPRESSION ( 2X ) GROUND STUDS LUGS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 88
PHASE B (E10) PHASE C (E11) GROUND E6, E7 , E8 COMPRESSION AC INPUT LUGS TO BYPASS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 89
PHASE B (E10) PHASE C (E11) E6, E7 , E8, E12 AC INPUT TO BYPASS ( 2X ) GROUND STUDS FOR CABINET TO GROUND COMPRESSION CABINET WIRING LUGS Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 90
PHASE B (E10) PHASE C (E11) E6, E7 , E8, E12 GROUND AC INPUT COMPRESSION TO BYPASS LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 91
If Four–Wire installation, connect the AC Output Neutral to the E12 Neutral terminals. See Figure 32 Figure 33 for Four–Wire power terminal details Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 92
BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION ( 2X ) GROUND STUDS LUGS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 93
BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 94
BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION ( 2X ) GROUND STUDS LUGS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 95
E5 ( - ) AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 96
If Four–Wire installation, connect the AC Output Neutral to the E12 Neutral terminals. See Figure 36 Figure 37 for Four–Wire power terminal details. 10. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 97
BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION ( 2X ) GROUND STUDS LUGS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 98
BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 99
BREAKER AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) ( 2X ) GROUND STUDS GROUND COMPRESSION FOR CABINET TO LUGS CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 100
E5 ( - ) AC OUTPUT TO LOAD PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 101
UPS System Installation Figure 38. RIB Terminal Detail AC Input to Rectifier Input Breaker PHASE A (RIB-1) PHASE B (RIB-3) PHASE C (RIB-5) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 102
Route and connect the battery cables between the UPS and battery cabinet or battery disconnect according to the instructions in the Eaton Samsung Gen 3 Battery Cabinet Installation and Operation Manual, Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton...
UPS interface terminal locations. Proceed to Step 13. Bottom Entry Wiring. Remove the bottom interface entry conduit landing plates to drill or punch holes (see Figure 41). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 104
16. Close the UPS outside door and secure the latch. Figure 39. Interface Terminal Locations Upper Cabinet View of UPS Minislot Communication Bays Interface Terminals Pull Chain and CAN Terminals Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Cabinet Stiffener Bar Minislot Communication Bay 1 Minislot Communication Bay 4 Relay Output Terminals Pull Chain and Host USB CAN Terminals Device USB REPO Terminals Building Alarm Terminals RS-232 Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
MIS - Aux COM MIS - Aux NC 2 lb in Twisted Pair Wires #14 #30 AWG #18 AWG (0.22-0.25 Nm) RIB - Aux COM RIB - Aux NC Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Aux COM - MBP 2 Aux NC - MBP 3 2 / 3 / 4 Breaker SIAC-B Aux COM - MIS 9 Aux NC - MIS 10 Front of UPS Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 111
15. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 16. If removed, reinstall the sidecar front panel and secure with the retained hardware. 17. Close the UPS outside door and secure the latch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
UPS System Installation Figure 46. Shunt Trip and Auxiliary Terminal Block (CN8) Location Shunt Trip and Auxillary Terminals for Battery and Bypass (CN8 Terminal Block) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 113
Table 26 for next option to install; otherwise, proceed to Step 17. 17. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
48 Vdc Battery Shunt Trip + 48 Vdc Battery Aux Input: Contacts used to monitor 1–A auxiliary contacts on battery 48 Vdc Battery Aux breaker or disconnect 1–B Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 115
10. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 11. If removed, reinstall the sidecar front panel and secure with the retained hardware. 12. Close the UPS outside door and secure the latch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 116
15. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 16. If removed, reinstall the sidecar front panel and secure with the retained hardware. 17. Close the UPS outside door and secure the latch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 117
Remove the cabinet stiffener bar (see Interface Terminal Locations) before installing or removing Minislot cards. Reinstall the bar after the procedure is completed. For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.9 Getting Help). To install wiring: If not already installed, install the LAN drop.
Page 118
Bottom Entry Wiring. Remove the bottom interface entry conduit landing plate to drill or punch holes (see Figure 41). 10. Reinstall the interface entry plate and install the conduit. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
14. Connect the REPO wiring as shown in Table 31 Figure 50 for a normally-open REPO or Table 32 Figure 51 for a normally-closed REPO for a normally-closed REPO. See paragraph 3.2.3 UPS System Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Make a copy of the Installation Checklist before filling it out, and retain the original. After the installation is complete, an Eaton Customer Service Engineer must verify the operation of the UPS system and commission it to support the critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters.
Page 123
Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) o Air conditioning equipment is installed and operating correctly. o The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) o Adequate workspace exists around the UPS and other cabinets.
U U P P S S S S y y s s t t e e m m O O v v e e r r v v i i e e w w The Eaton 93PM Gen 2 UPS is a continuous-duty, solid-state, transformerless, three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
3. DASHED LINES OUTSIDE OF UPS INDICATE OPTIONAL EQUIPMENT CABINETS. BREAKER 4. BACKFEED PROTECTION IS NOT PROVIDED AS A PART OF UPS. CUSTOMER SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
UPS Oneline Schematics Figure 58. Eaton 93PM Gen 2 Three-Wire UPS with Top Entry Sidecar System Oneline Parallel CAN Pull Chain AC INPUT TO AC INPUT TO RECTIFIER BYPASS Mini-Slot (SOURCE 1) (SOURCE 2) Remote EPO Interface Interface Board E1,E2,E3...
UPS Oneline Schematics Figure 59. Eaton 93PM Gen 2 Three-Wire UPS with Bypass Sidecar (SIAC-B) System Oneline Parallel CAN Pull Chain AC INPUT TO AC INPUT TO RECTIFIER BYPASS Mini-Slot (SOURCE 1) (SOURCE 2) Remote EPO Interface Interface Board E1,E2,E3...
U U s s i i n n g g t t h h e e C C o o n n t t r r o o l l P P a a n n e e l l The following paragraphs describe the UPS control panel, including controls and indicators, and how to monitor UPS operation. The control panel is shown in Figure Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
The four symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED) lamps work with the alarm horn to provide the operating status of the UPS. Table 33 describes the status indicators. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
All functions and commands are accessed by touching or tapping the screen tabs or buttons. When text input is required, either a Qwerty keyboard or numeric keypad will be displayed. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
The UPS navigation tab menu bar allows you to display data in the information area to help you monitor and control UPS operation. Table 34 shows the basic menu structure. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation of the operating status of the system. Figure 63. Main Menu and Mimic Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
The end of the log (the most recent events) is displayed first; scroll upward to view older event listings. To scroll through the events, press the up or down scroll bar. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Statistics Details Tap the desired statistic button to display the detailed statistic screen. Controls See paragraph 7.2.8 System Controls for details. Figure 64. Typical Meters Summary Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
7 7 . . 2 2 . . 7 7 S S i i g g n n I I n n The Controls and Setting screens are restricted. The user must sign in using a password to gain access. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Level 1 default password is 111111. Settings Level 2 default password is 101010. Sign in is complete. Tap continue to return to previous screen. Figure 73. Sign In Password Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Bypass mode from Double Conversion mode. Charger TURN ON CHARGER/TURN OFF CHARGER sets the battery charger on or off. Battery Test RUN BATTERY TEST starts the battery test. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
UPS Operating Instructions Figure 78. Typical UPM Control Screen Figure 79. Typical EAA Control Screen Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 150
Verify no alarms are active. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed. Tap the GO TO BYPASS button. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Press the DC Start button on the front of each UPM to power on the UPM power supply. (See Figure 80 for DC Start Button location). Figure 80. DC Start Button Location DC Start Button 10. Close the door and secure the latch. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 152
Tap the MODULES CONTROLS tab on the secondary Control menu navigation bar. The UPM Select screen is displayed. On the UPM Select screen, select the UPM to start. The UPM Control Screen is displayed. Tap the START MODULE button. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 153
Tap the EAA CONTROLS tab on the secondary Control menu navigation bar. The EAA CONTROLS screen is displayed. Tap the DISABLE ESS button. The UPS transfers to Double Conversion mode. The NORMAL status indicator is illuminated. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 154
7 7 . . 3 3 . . 1 1 2 2 S S i i n n g g l l e e U U P P M M R R e e s s t t a a r r t t To restart a single UPM from a shutdown state: Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 155
Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Tap the TURN OFF CHARGER button. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 156
To restart the UPS after using the LOAD OFF follow the procedure in paragraph 7.3.1 Starting the UPS in Double Conversion Mode 7.3.2 Starting the UPS in Bypass Mode. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 157
To use the REPO switch: Firmly push the red pushbutton until it locks into place. The switch latches into the activated state (see Figure 81). Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 158
Attendez au moins 5 minutes avant d'accéder aux composants internes. Figure 81. REPO Operation Activated Deactivated (Pushbutton locked into place.) (Unlock pushbutton to release.) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
M M i i n n i i s s l l o o t t C C a a r r d d s s The Eaton 93PM Gen 2 UPS has four standard, factory-installed Minislot communication bays. The UPS is...
Page 160
It’s also powered by CA Technologies, bringing together the best in hardware and software. PredictPulse Service is included at no charge during the first year of Eaton 93PM Gen 2 UPS operation (warranty period) along with the required connectivity parts. Beyond that, it may be purchased with Eaton Support Agreements or as a standalone subscription after the initial warranty expires.
Page 161
Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
Each battery string is an energy source in itself. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. Observe these precautions when working on or around batteries: •...
Page 163
Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated or the Normal status indicator is not illuminated, contact an Eaton service representative. 9 9 . . 2 2 . . 2 2 M M O O N N T T H H L L Y Y M M a a i i n n t t e e n n a a n n c c e e...
Page 164
à fonctionner sans filtres installés. Close the front door and secure the latch. Record maintenance results and any corrective actions in a suitable log. Figure 83. Air Filter Location Air Filter Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 165
9 9 . . 2 2 . . 4 4 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
Page 166
M M a a i i n n t t e e n n a a n n c c e e T T r r a a i i n n i i n n g g A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance.
Page 167
Eaton 93PM Gen 2 150-3 (N+1) Eaton 93PM Gen 2 150-2 90 kW Eaton 93PM Gen 2 150-3 (N+1) Eaton 93PM Gen 2 150-2 100 kW Eaton 93PM Gen 2 150-3 (N+1) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Output Voltage Phase Displacement < 2.5° for 100% maximum load imbalance (linear load) Frequency Regulation 0.1 Hz free running Synchronous to Bypass ± 4 Hz (default setting) Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 169
Meets IEC 61000-4-2 Level 3 specifications and CISPR 24. Withstands up to 4 kV (ESD) contact pulse without damage and with no disturbance or adverse effect to the critical load. Eaton 93PM Gen 2 150 kW UPS Installation and Operation Manual P-164001030—Rev 01...
Page 170
C C h h a a p p t t e e r r 1 1 1 1 W W a a r r r r a a n n t t y y To view the UPS warranty please click on the link or copy the address to download from the Eaton website: UPS Product Warranty https://www.eaton.com/content/dam/eaton/products/backup-power-ups-surge-it-power-distribution/backup-...