Figure 5: Major Components Of The Centric 3X480 Vac (240 Kw Model); Table 1: Key To Figure 5 - Gamatronic Centric 3X480 VAC Installation Manual

For the 120 kw and 240 kw models
Hide thumbs Also See for Centric 3X480 VAC:
Table of Contents

Advertisement

240 kW model, front view

Figure 5: Major components of the Centric 3x480 Vac (240 kW model)

I
D
TEM
ESCRIPTION
A
The UPS cabinet's front door
B
Back side of the LCD panel.
C
System controller
Shelves for up to 8 UPS modules. Each UPS module supplies 30 kW.
D
The lowest UPS shelf is UPS shelf 1, the next shelf up is shelf 2, and so on.
Shelves for up to 4 dc-dc converter modules. The dc-dc modules convert the battery voltage of
270 V to 400 V for the UPS modules. Each dc-dc module contains 2 converter blocks. All of the
E
dc-dc blocks are connected to one-another in parallel, and supply the UPS modules in parallel.
The lowest dc-dc shelf is shelf 1; the next shelf up is dc-dc shelf 2, and so on.
F
The static switch is located at this level, inside the UPS. It is not visible from the outside.
G
Main ac terminals. See Figure 9 for details.
H
Neutral bus bar.
Protective Earth Ground bus bar
I
6
G
E
AMATRONIC
LECTRONIC

Table 1: Key to Figure 5

I
L
.
NDUSTRIES
TD
240 kW model, rear view
Centric 3x480 Vac, Installation Guide, rel. 2.2

Advertisement

Table of Contents
loading

Table of Contents